MAXIMUM OVERCURRENT PROTECTION AMPACITY

This rating specifies the proper overcurrent protection ampacity.

OBDC breakers are panel-mount circuit breakers.

Class T DC fuses are terminal-mounted and should always be used in conjuncture with a disconnect mechanism.

FXs used in home installations should use properly sized DC circuit breakers.

A DC breaker includes both overcurrent protection and disconnect capability.

OutBack Power Systems recommends Class T fuses for marine installations where a DC disconnect is not required.

MODEL

AMPACITY

DC BREAKER

DC FUSE

 

 

 

 

FX2012(M)T

260 amps

OBDC-250

Class T-400 (Mobile Only)

 

 

 

 

FX2024(M)T

175 amps

OBDC-175

Class T-300 (Mobile Only)

 

 

 

 

FX2532(M)T

175 amps

OBDC-175

Class T-300 (Mobile Only)

 

 

 

 

FX2548T

100 amps

OBDC-100

Not Recommended

 

 

 

 

VFX2812(M)

260 amps

OBDC-250

Class T-400 (Mobile Only)

 

 

 

 

VFX3524(M)

260 amps

OBDC-250

Class T-400 (Mobile Only)

 

 

 

 

VFX3232(M)

175 amps

OBDC-175

Class T-300 (Mobile Only)

 

 

 

 

VFX3648

175 amps

OBDC-175

Not Recommended

 

 

 

 

WIRE SIZES

The following chart contains information on wire sizes, the DC resistance of the wires and the corresponding diameters and areas of these wires. This information can be used to calculate the

voltage drop of the wires or to find

an equivalent

wire size.

 

 

 

 

 

 

 

 

 

SIZE

DC

 

CROSS-SECTIONAL AREA

APPROXIMATE DIAMETER

 

(AWG)

 

 

 

 

 

 

 

Resistance in Ohms

 

 

 

 

 

 

 

(1000 feet)

 

 

 

 

 

 

 

INCHES

 

MILLIMETERS

INCHES

MILLIMETERS

 

 

 

14

3.14

 

.0032

 

2.08

.078

1.98

12

1.98

 

.0051

 

3.31

.101

2.57

10

1.24

 

.0082

 

5.26

.126

3.20

8

0.78

 

.0130

 

8.37

.162

4.11

6

0.50

 

.0206

 

13.30

.215

5.46

4

0.31

 

.0328

 

21.15

.269

6.83

2

0.19

 

.0521

 

33.62

.337

8.56

1

0.15

 

.0657

 

42.41

.376

9.55

1/0

0.12

 

.0829

 

53.50

.423

10.74

2/0

0.10

 

.1045

 

67.43

.508

12.90

3/0

0.08

 

.1318

 

85.01

.576

14.63

4/0

0.06

 

.1662

 

107.20

.645

16.38

32

Page 35
Image 35