Outback Power Systems FX 2024 T AC Wiring Notes for the Mobile FX, AC Neutral OUT/AC Neutral

Models: FX 2024 T

1 40
Download 40 pages 4.08 Kb
Page 17
Image 17

AC WIRING NOTES FOR THE MOBILE FX

AC HOT OUT

Supplies the AC hot output conductors through a 30 amp maximum AC branch rated circuit breaker using 6 AWG wire and connect to the AC

AC NEUTRAL OUT/AC NEUTRAL IN

Connects the AC neural input conductor to the AC NEUTRAL IN terminal.

Connects the AC neutral output conductor to the AC NEUTRAL OUT terminal.

Do not assume these terminals are common in the Mobile FX.

����������

��������������

��������������

� � � � � � � � � � � � �

� � � � � � � � � �

� � � � � � � � � � � � � � � �

���������������

CHASSIS GROUND

Connects both the AC input and AC output ground conductors to the CHASSIS GROUND and NEU/GROUND BOND terminals.

If there is only one Mobile FX in the system, leave the copper bus (provided) installed between the CHASSIS GROUND and NEU/ GROUND BOND terminals. If there is more than one Mobile FX in the system, remove

the copper bus from every Slave FX.

AC HOT IN

The AC hot input conductor (black) must be supplied through a 30 amp maximum AC branch rated circuit breaker and connected to the AC HOT IN.

6 AWG wire is required for the FX’s AC transfer switch.

 

�������������

 

 

 

 

���������

 

 

��������������� ��������

������

����

����

����

����

 

��������������

 

 

��������

 

 

�����������

��

���

��������

��������

 

�����

�����

������

 

 

������

14

Page 17
Image 17
Outback Power Systems FX 2024 T installation manual AC Wiring Notes for the Mobile FX, AC Neutral OUT/AC Neutral