The STATUS screens allow the system user to check the operation of the FX system. Both AC voltage and AC current meters are provided to enable monitoring, adjustment and troubleshooting of the system operation.
The MODES section lets the user view and change the various modes for a specific FX by pressing the PORT to access a specific FX. The modes include inverter, ac in, charger, auxiliary, and equalize. The operation of these modes can be changed by selecting the CHANGE MODE option on the screen. This is helpful if the user wishes to quickly enable or disable a particular function of a specific FX if necessary.
6:54:42P
SUM STATUS SETUP ADV
↓
choose product:
FX MX
↓
choose category:
MODES METER BATT PG2
↓
inv control: ON CHANGE
DOWN STAT MODE PORT
↓
CHANGE
DOWN UP MODE PORT
↓
chr control: AUTO CHANGE
DOWN UP MODE PORT
↓
aux control: AUTO CHANGE
DOWN UP MODE PORT
↓
eq enabled: No
CHANGE
UP MODE PORT
The MAIN screen is where the menu system starts. The four words in the bottom line of the display correspond to the four buttons located below the display. The word in BOLD on the bottom line indicates the selection used to advance the display to the next screen. Pressing the left two buttons simultaneously from anywhere in the menu will return you to this screen.
Selecting <STATUS> allows selection of the product type:
<FX> | FX inverter/charger system |
MX | MX60 PV MPPT charge controller |
<MODES> | Shows status and allows adjustment of Inverter, AC input, Charger, Aux, and EQ |
METER | Provides the AC voltages and currents of the FX |
BATT | Provides the battery voltage and charger set points and timers |
PG2 | Displays additional sections – ERRORS, WARNINGS and PG3 |
The INV CONTROL screen lets you see the status of the inverter function of the FX. Pressing the STAT button returns you to the first page of the status menu. Pressing the CHANGE MODE button opens a screen that gives the options of turning the inverter OFF, turning the inverter ON, or putting the inverter into SEARCH. Pressing PORT will access the next FX if a HUB is present.
The AC IN CONTROL screen lets you see if the FX will accept an AC source at its input terminals. Pressing the UP button returns you to the previous page of the MODES menu. Pressing the CHANGE MODE button opens a screen that gives the options of rejecting an AC source by pressing DROP or accepting an AC source by pressing USE. Pressing PORT will access the next FX if a HUB is present.
The CHR CONTROL screen lets you see what mode the charger is in. Pressing the UP button returns you to the previous page of the MODES menu. Pressing the CHANGE MODE button opens a screen that gives the options of turning the charger OFF or putting the charger into AUTO where it will follow the
The AUX CONTROL screen lets you see the status of the auxiliary output. Pressing the UP button returns you to the previous page of the MODES menu. Pressing the CHANGE MODE button opens a screen that gives the options of turning the Aux OFF, turning the Aux ON, or putting the Aux into AUTO mode. In AUTO mode it will follow the “Aux Output Function” and its parameters that can be set in the Advanced (ADV) menu. Pressing PORT will access the next FX if a HUB is present.
The EQ ENABLED screen lets you see if the FX is in an equalize charging cycle and can also start or stop a cycle. Pressing the UP button returns you to the previous page of the MODES menu. Pressing the CHANGE MODE button opens a screen that gives the options of START or STOP to initiate or cancel an equalize charge. Pressing PORT will access the next FX if a HUB is present.
Copyright 2003 OutBack Power Systems, Inc. | FX & VFX “E” Series Inverter/Charger System | Installation & Programming Manual |