RATINGS
MAXIMUM CONTINUOUS OUTPUT POWER: Varies with model number of the inverter:
EXPORT VERSIONS
FX2012ET | 2000 VA |
FX2024ET | 2000 VA |
FX2348ET | 2300 VA |
VFX2612E | 2600 VA |
VFX3024E | 3000 VA |
VFX3048E | 3000 VA |
MAXIMUM AC OUTPUT FAULT CURRENT:
The FX will go into fault if a sustained current draw of 25 amps RMS when operating as an inverter. When passing an AC source through the FX via the AC transfer switch, the maximum AC output fault current will be determined by the AC source.
NOMINAL DC VOLTAGE OUTPUT:
The last two digits in the model number designate the nominal DC voltage.
Example: FX2324ET – 24V DC Voltage.
MAXIMUM OVERCURRENT PROTECTION AMPACITY:
EXPORT | AMPACITY | DC BREAKER | DC FUSE |
FX2012ET | 250 amps | ||
FX2024ET | 175 amps | ||
FX2348ET | 100 amps | ||
VFX2612E | 250 amps | ||
VFX3024E | 175 amps | ||
VFX3048E | 175 amps |
OBDC are panel mount circuit breakers. SMF are DC terminal mounted fuses and should always be used in conjuncture with a disconnect. FX’s used in home installations should use properly sized DC breakers. A DC breaker includes both overcurrent protection and disconnect capability. SMF fuses are used primarily for marine installations where a DC disconnect is not required.
Copyright 2003 OutBack Power Systems, Inc. | FX & VFX “E” Series Inverter/Charger System | Installation & Programming Manual |
19009 62nd Ave NE, Arlington WA 98223 USA |
| Page 9 |