MATE - ADVANCED / CALIBRATION

The CAL (calibration) section is used in the factory or field to make fine adjustments in the operation of the FX. It is particularly useful when multiple FX’s are connected together in the different stacking configurations to maximize the performance of the FX’s.

In most cases, the user will not need to adjust these settings from the factory default values.

ADV/FX/PAGE1--------

choose category:

ADV

INV

CHGR

PG2

 

 

 

ADV/FX/PAGE2--------

choose category:

 

PG1

GRID

GEN

PG3

 

 

 

ADV/FX/PAGE3--------

choose category:

 

PG2

AUX

STACK

PG4

 

 

 

ADV/FX/PAGE4--------

choose category:

PG3 SELL CAL MAIN

ADV/FX/CALIBRATE-P00

vac input 230 vac adjustment

DOWN INC DEC PORT

ADV/FX/CALIBRATE-P00 vac output 230 vac adjustment

DOWN INC DEC PORT

ADV/FX/CALIBRATE-P00 battery vdc 12.8 vdc adjustment

DOWN INC DEC PORT

ADV/FX/CALIBRATION-- calibration setup completed

TOP ADV MAIN

Once the password has been correctly entered, the ADV - CHOOSE CATEGORY: screen is displayed. Selecting <PG2> shows a second screen of categories.

Selecting <PG3> shows a third screen of categories.

Selecting <PG4> shows a fourth screen of categories.

Selecting <CAL> allows calibration of the AC input, AC output, and battery voltage set points.

The VAC INPUT ADJUSTMENT allows calibration of the AC input voltage. If the AC source is measured and is different than the value read from the MATE, the user can adjust the reading to match the measured value. This value can be raised by pressing the INC button. Conversely, this value can be lowered by pressing the DEC button. The value can be raised or lowered 4 vac.

The VAC OUTPUT ADJUSTMENT allows calibration of the AC output voltage. If the AC output is measured and is different than the value read from the MATE, the user can adjust the reading to match the measured value. This value can be raised up to 4 vac by pressing the INC button and lowered up to 4 vac by pressing the DEC button. NOTE: Only affects MATE's voltage display - See page 44 [ADJ. OUTPUT VOLTAGE] for actual adjustment of inverter VAC output.

The BATTERY VDC ADJUSTMENT allows calibration of the battery voltage. If the battery voltage is measured and is different than the value read from the MATE, the user can adjust the reading to match the measured value. This value can be raised by pressing the INC button. Conversely, this value can be lowered by pressing the DEC button. The value can be raised or lowered 0.2 vdc.

Selecting TOP returns the user to the top of the ADV/FX/CALIBRATION menu section. Selecting ADV returns you to the advanced screen to allow selection of another product connected to the MATE. Selecting MAIN returns the display to the MAIN screen.

END OF ADVANCED MENU SYSTEM