WIRE SIZES

The following chart contains information on wire sizes, the DC resistance of the wires and the corresponding diameters and areas of these wires. This information can be used to calculate the voltage drop of the wires or to find an equivalent wire size.

 

SIZE

 

 

DC

 

 

CROSS-SECTIONAL AREA

 

 

APPROXIMATE

 

 

 

 

 

Resistance

 

 

 

 

DIAMETER

 

 

(AWG)

 

 

 

 

 

 

 

 

 

 

 

 

in Ohms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SQUARESQUARE

 

INCHES

 

 

MILLIMETERS

 

 

 

 

 

(1000 feet)

 

 

 

 

 

 

 

 

 

 

 

 

INCHES

MILLIMETERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

3.14

 

.0032

2.08

 

.078

 

1.98

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

1.98

 

.0051

3.31

 

.101

 

2.57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

1.24

 

.0082

5.26

 

.126

 

3.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

0.78

 

.0130

8.37

 

.162

 

4.11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

0.50

 

.0206

13.30

 

.215

 

5.46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

0.31

 

.0328

21.15

 

.269

 

6.83

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

0.19

 

.0521

33.62

 

.337

 

8.56

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

0.15

 

.0657

42.41

 

.376

 

9.55

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/0

 

0.12

 

.0829

53.50

 

.423

 

10.74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2/0

 

0.10

 

.1045

67.43

 

.508

 

12.90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/0

 

0.08

 

.1318

85.01

 

.576

 

14.63

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4/0

 

0.06

 

.1662

107.20

 

.645

 

16.38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation & Programming Manual

FX & VFX “E” Series Inverter/Charger System

Copyright 2003  OutBack Power Systems, Inc.

 

 

19009 62nd Ave NE, Arlington WA 98223 USA

Page 54

Rev 7.0

07/02/04