RATINGS

MAXIMUM SYSTEM AC VOLTAGE:

 

Single phase

230

VAC at 50 Hz

Parallel stacked

230

VAC at 50 Hz per AC output leg

Three Phase

230

VAC at 50 Hz per AC output leg (limit three)/400 VAC at 50 Hz between AC output legs

RECOMMENDED DC VOLTAGE RANGE:

12V systems

11 – 16 VDC

24V Systems

22 – 32 VDC

48V Systems

44 – 64 VDC

MAXIMUM DC INPUT CURRENT: 12V units = 600 amps / 24 V units = 300 amps / 48V units = 150 amps

This is the most sustained current the FX will draw when starting very large AC loads. It is not used for sizing the DC disconnect or selecting DC cable gauge. It is used to select the minimum reasonable battery capacity.

AC INPUT OPERATING VOLTAGE RANGE: 200-260 VAC

Voltages outside of this range may damage AC loads connected to the FX’s AC output.

MAXIMUM AC INPUT CURRENT: 30 amps at 230 VAC 50 Hz

The AC input on the FX supplies power for two separate internal AC circuits – the AC transfer switch and the battery charging system. The battery charger will “back off” when the combined total of the AC load and the battery charger exceed the programmed AC input current limit. The FX’s default setting for this parameter is 24 amps.

RECOMMENDED MAXIMUM AC PASS THROUGH CURRENT:

30 amps at 230 VAC 50 Hz for each FX

MAXIMUM AC CURRENT FOR AC BATTERY CHARGER:

FX “E” series: 7 amps AC at 230 VAC maximum

VFX “E” series: 10 amps AC at 230 VAC maximum

Note: Factory settings are 4 amps AC for the Export version.

OPERATING FREQUENCY RANGE:

The FX will accept an AC source within the frequency range of 45 - 55 Hz. Once the FX connects to the AC source, if the frequency goes outside of the range 45 - 55 Hz, the FX will record a warning. If the frequency of the AC source is outside of the range of 41-59 Hz, then the FX will drop the AC source.

NOMINAL AC OUTPUT VOLTAGE:

One FX will provide 230 VAC 50 Hz single phase

Two or more FX’s may be parallel stacked for 230 VAC 50 Hz single phase

Three FX’s can be 3-phase stacked for 230/400 VAC 50 Hz

MAXIMUM AC OUTPUT CURRENT:

35 amps Peak (for 160 milliseconds) current limit

Inverter will shut down after 5 seconds of operation in current limit

Installation & Programming Manual

FX & VFX “E” Series Inverter/Charger System

Copyright 2003  OutBack Power Systems, Inc.

 

 

19009 62nd Ave NE, Arlington WA 98223 USA

Page 8

Rev 7.0

07/02/04

Tel 360 435 6030 Fax 360 435 6019