This manual contains important instructions for the OutBack FX “Export” (or “E”) series inverter/charger system with the software which allows parallel and
1All of the AC field wiring terminals are to be torqued to 30
2Torque the DC connections to 60
use a crimp on type ring terminal or compression type lug. Cable must meet the requirements of the National Electrical Code. Use of large gauge cables {2/0 AWG (68mm2) or 4/0 AWG (107mm2)} or larger is advisable to reduce losses and ensure high performance of the FX. Cables of too small a gauge can result in poor performance and even damage the FX. Keep the cables together as much as possible and ensure that both cables pass through the same knockout and conduit fittings to allow the magnetic fields of the cables to cancel.
3For equipment grounding hook up, see wiring instructions in this manual. This product is intended to be installed as part of a permanently grounded electrical system.
4AC overcurrent protection for all connections must be provided by others as part of the installation.
5DC battery circuit overcurrent protection must be provided by others as part of the installation.
OutBack offers 100, 175 and 250 amp DC breaker (part number
6 The equipment ground on the inverter is marked with this symbol:
7 This inverter has a single phase output. It is marked with this symbol:
8 This inverter puts out a sine wave waveform. It is marked with this symbol:
9CAUTION: To reduce the risk of fire, connect only to a circuit provided with 30 amp maximum