11 Installation Instruction

11.1. Select The Best Location

11.2. Indoor/Outdoor Unit

INDOOR UNIT

Installation Diagram

 

Do not install the unit in excessive oil fume area such as kitchen, workshop and etc.

There should not be any heat source or steam near the unit.

There should not be any obstacles blocking the air circulation.

A place where air circulation in the room is good.

A place where drainage can be easily done.

A place where noise prevention is taken into consideration.

Do not install the unit near the door way.

Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.

Recommended installation height for indoor unit shall be at least 2.5 m.

OUTDOOR UNIT

If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed.

There should not be any animal or plant which could be affected by hot air discharged.

Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.

Do not place any obstacles which may cause a short circuit of the discharged air.

If piping length is over the rated length, additional refrigerant should be added as shown in the table.

 

Piping size

Rated

Max

Min.

Max.

Additional

Model

Length

Elevation

Piping

Piping

Refrigerant

 

 

(m)

(m)

Length

Length

(g/m)

 

 

 

 

Gas

Liquid

 

 

 

(m)

(m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CE7HKE,

3/8”

1/4”

7.5

15

3

15

20

CE9HKE

 

 

 

 

 

 

 

 

CE12HKE

1/2”

1/4”

7.5

15

3

15

20

 

 

 

 

 

 

 

 

Example: For CE7HKE

If the unit is installed at 10 m distance, the quantity of additional refrigerant should be 50g ...... (10 - 7.5) m x 20 g/m = 50 g

30