[Heating]

• According to indoor pipe temperature, automatic heating fan speed is determined as follows.

B. Feedback control

Immediately after the fan motor started, feedback control is performed once every second.

During fan motor on, if fan motor feedback 2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error counter increase, fan motor is then stop and restart. If the fan motor counter becomes 7 times, then H19 - fan motor error is detected. Operation stops and cannot on back.

12.3. Outdoor Fan Motor Operation

Outdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.

12.4. Airflow Direction

1.There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).

2.Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using remote control).

12.4.1. Vertical Airflow

Operation Mode

Airflow Direction

 

 

 

 

Vane Angle (θ)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

 

3

 

4

5

 

 

 

 

 

 

 

 

 

 

 

Heating

Auto with Heat Exchanger

 

A

Upward fix

 

 

0

 

 

 

 

Temperature

 

 

 

 

 

 

 

 

 

 

 

 

B

Downward fix

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

Upward fix

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

Downward fix

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual

 

 

12

25

 

37

 

49

60

 

 

 

 

 

 

 

 

 

 

 

Cooling and Ion

Auto

 

 

 

 

10 ~ 32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual

 

 

12

18

 

25

 

31

37

 

 

 

 

 

 

 

 

 

 

 

Soft Dry

Auto

 

 

 

 

10 ~ 32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual

 

 

12

18

 

25

 

31

37

 

 

 

 

 

 

 

 

 

 

 

 

1.Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated above. For heating mode operation, the angle of the vane depands on the indoor heat exchanger temperature as Figure 1 below. When the air conditioner is stopped using remote control, the vane will shift to close position.

39