e.Indicator
•When Patrol operation starts, Patrol Sensor indicator ON.
•When
f. Remote Control Receiving Sound |
| |
• Normal Operation ο Patrol Mode | : Beep | |
• Patrol Mode | ο Stop | : Long Beep |
• Patrol Mode | ο Normal Operation : Beep | |
• Stop | ο Patrol | : Beep |
g. Timer Control
•When ON timer activates when unit stops, previous operation resumes without Patrol operation.
•When ON timer activates during any operation, no change and carry on current operation.
•When OFF timer activates during any operation, all operation stops.
h. Power failure
•During Patrol individual operation, if power failure occurs, after power resumes, Patrol individual operation resumes immediately.
•During combination operation, if power failure occurs, after power resumes combination operation resume immediately.
12.12.
A. Purpose
This operation provides clean air by producing negative ions to attract dust captured at the positively charged
B. Control Condition
a.
•During unit running at any operation mode, if
•During unit is OFF, if
b.
•When “OFF/ON” button is pressed to stop the operation.
•When
•When “Patrol” button is pressed.
•When OFF Timer activates.
c.
•When indoor fan stop (during deice, odor cut control, thermostat off, etc.).
•When indoor intake temperature 40θC.
44