15.3.Error Codes Table

Diagnosis

Abnormality / Protection control

Abnormality

Emergency

Primary location to verify

display

Judgement

operation

 

 

 

 

 

 

 

 

H00

No abnormality detected

Normal operation

 

 

 

 

 

 

H11

Indoor / outdoor abnormal

> 1 min after starting

Indoor fan operation

• Internal / external cable connections

 

communication

operation

only

• Indoor / Outdoor PCB

 

 

 

 

 

H12

Connection capability rank abnormal

 

 

 

 

 

H14

Indoor intake air temperature sensor

Continue for 5 sec.

• Intake air temperature sensor

 

abnormality

 

 

(detective or disconnected)

 

 

 

 

 

H15

Outdoor compressor temperature

Continue for 5 sec.

• Compressor temperature sensor

 

sensor abnormality

 

 

(detective or disconnected)

 

 

 

 

 

H16

Outdoor Current Transformer open

• Outdoor PCB

 

circuit

 

 

• IPM (Power transistor) module

 

 

 

 

 

H19

Indoor fan motor merchanism lock

7 times occurance

• Indoor PCB

 

 

continuously.

 

• Fan motor

 

 

 

 

 

H23

Indoor heat exchanger temperature

Continue for 5 sec.

O

• Heat exchanger temperature sensor

 

sensor abnormality

 

(Cooling only)

(defective or disconnected)

 

 

 

 

 

H25

E-Ion breakdown

• Indoor PCB

 

 

 

 

E-Ion PCB

 

 

 

 

 

H27

Outdoor air temperature sensor

Continue for 5 sec.

O

• Outdoor temperature sensor

 

abnormality

 

 

(defective or disconnected)

 

 

 

 

 

H28

Outdoor heat exchanger temperature

Continue for 5 sec.

O

• Outdoor heat exchanger

 

sensor abnormality

 

 

temperature sensor (defective or

 

 

 

 

disconnected)

 

 

 

 

 

H33

Indoor/Outdoor wrong connection

• Indoor/Outdoor supply voltage

 

 

 

 

 

H38

Indoor/outdoor mismatch (brand code)

 

 

 

 

 

H58

Abnormal gas sensor

Continue for 6 hours

• Gas sensor

 

 

 

 

(defective or disconnected)

 

 

 

 

 

H98

Indoor high pressure protection

• Air filter dirty

 

 

 

 

• Air circulation short circuit

 

 

 

 

 

H99

Indoor heat exchanger anti-freezing

• Insufficient refrigerant

 

protection

 

 

• Air filter dirty

 

 

 

 

 

F11

Cooling / Heating cycle changeover

4 times occurance

4-way valve

 

abnormality

within 30 minutes

 

V-coil

 

 

 

 

 

F90

PFC control

4 times occurance

• Voltage at PFC

 

 

within 20 minutes

 

 

 

 

 

 

 

F91

Refrigeration cycle abnormal

2 times occurance

• No refrigerant

 

 

within 20 minutes

 

(3-way valve is closed)

 

 

 

 

 

F93

Outdoor compressor abnormal

4 times occurance

• Outdoor compressor

 

revolution

within 20 minutes

 

 

 

 

 

 

 

F95

Cool high pressure protection

4 times occurance

• Outdoor refrigerant circuit

 

 

within 20 minutes

 

 

 

 

 

 

 

F96

IPM (power transistor) overheating

• Excess refrigerant

 

protection

 

 

• Improper heat radiation

 

 

 

 

• IPM (Power transistor)

 

 

 

 

 

F97

Outdoor compressor overheating

4 times occurance

• Insufficient refrigerant

 

protection

within 20 minutes

 

• Compressor

 

 

 

 

 

F98

Total running current protection

3 times occurance

• Excess refrigerant

 

 

within 20 minutes

 

• Improper heat radiation

 

 

 

 

 

F99

Outdoor Direct Current (DC) peak

7 times occurance

• Outdoor PCB

 

detection

continuously

 

• IPM (Power transistor)

 

 

 

 

• Compressor

 

 

 

 

 

Note:

“O” - Frequency measured and fan speed fixed.

The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard following by pressing the “CHECK” button at Remote Control.

Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound is

changed from one “beep” to four “beep” sounds.

56