8.1.2.Compressor Operation Frequency

 

Intake Air Temperature - Internal Setting Temperature (°C)

 

Freq. H

 

Zone

Cooling & Soft Dry

Heating

Cooling

Soft Dry

Heating

Remark

1

-2.0

1.5

1

1

1

 

 

 

 

 

 

 

 

2

-1.5

1.0

1

1

1

 

 

 

 

 

 

 

 

3

-1.0

0.5

14

8

11

 

4

-0.5

0.0

20

8

15

 

 

 

 

 

 

 

 

5

0.0

-0.5

27

8

22

 

6

0.5

-1.0

35

11

27

 

 

 

 

 

 

 

 

7

1.0

-1.5

43

11

36

 

 

 

 

 

 

 

 

8

1.5

-2.0

46

11

39

Fc, Fh

9

2.0

-2.5

46

11

39

Fc, Fh

 

 

 

 

 

 

 

10

2.5

-3.0

46

11

39

Fc, Fh

11

Nil

-3.5

Nil

Nil

39

Fh

 

 

 

 

 

 

 

12

Nil

-4.0

Nil

Nil

39

Fh

 

 

 

 

 

 

 

Operating Frequency Calculation Formula:

CompHz = Freq. A × Freq. H + Freq. C

Example Calculation:

Model No.: E18CK

Operation Mode: Cooling

When Intake Air Temperature - Internal setting Temperature: 1.5°C

CompHz = Freq. A × Freq. H + Freq. C

=1.53 × 46 + 2.5

=72 Hz (It cuts down less than a decimal point)

Cooling & Soft Dry

 

 

 

E18CK

 

E21CK

 

 

 

 

 

Freq. A

 

Freq. C

 

Freq. A

Freq. C

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Load (Freq. H

9)

1.2

 

5.0

1.7

 

7.0

 

 

 

 

 

 

 

 

 

 

 

 

High Load (Freq. H > 10)

1.53

 

2.5

2.0

 

4.0

 

 

 

 

 

 

 

 

 

 

 

Heating

 

 

 

E18CK

 

E21CK

 

 

 

 

 

Freq. A

Freq. C

Freq. A

Freq. C

 

 

 

 

 

 

 

 

 

 

 

 

Low Load (Freq. H

11)

 

1.6

 

8.0

 

1.9

 

7.0

 

 

 

 

 

 

 

 

 

 

 

High Load (Freq. H > 12)

 

2.2

 

1.0

 

2.35

 

1.0

 

 

 

 

 

 

 

 

Freq. Range

 

 

 

E18CK

 

E21CK

Cooling

Fc

 

 

 

 

72

 

 

96

 

 

 

 

 

 

 

Operation Range

 

 

12 ~ 86

 

12 ~ 102

 

 

 

 

 

 

 

 

 

 

Heating

Fh

 

 

 

 

86

 

 

92

 

Operation Range

 

 

14 ~ 128

 

14 ~ 128

 

 

 

 

 

 

 

 

 

 

 

 

 

Remarks:

When Freq. H is equal to 46 (Cooling), 39 (Heating) or above, the Comp. may run at the freq. higher than Fc or Fh up to max. freq. operation.

Best Amenity Control

Every 90s (Cooling), 120s (Heating) maintain same zone Freq. H + 1 until Fc (46), Fh (39).

8.1.3.Cooling Operation8.1.3.1.Thermostat control

Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C.

Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF point +0.5°C.

17