| Intake Air Temperature - Internal Setting Temperature (°C) |
| Freq. H |
| ||
Zone | Cooling & Soft Dry | Heating | Cooling | Soft Dry | Heating | Remark |
1 | 1.5 | 1 | 1 | 1 |
| |
|
|
|
|
|
|
|
2 | 1.0 | 1 | 1 | 1 |
| |
|
|
|
|
|
|
|
3 | 0.5 | 14 | 8 | 11 |
| |
4 | 0.0 | 20 | 8 | 15 |
| |
|
|
|
|
|
|
|
5 | 0.0 | 27 | 8 | 22 |
| |
6 | 0.5 | 35 | 11 | 27 |
| |
|
|
|
|
|
|
|
7 | 1.0 | 43 | 11 | 36 |
| |
|
|
|
|
|
|
|
8 | 1.5 | 46 | 11 | 39 | Fc, Fh | |
9 | 2.0 | 46 | 11 | 39 | Fc, Fh | |
|
|
|
|
|
|
|
10 | 2.5 | 46 | 11 | 39 | Fc, Fh | |
11 | Nil | Nil | Nil | 39 | Fh | |
|
|
|
|
|
|
|
12 | Nil | Nil | Nil | 39 | Fh | |
|
|
|
|
|
|
|
Operating Frequency Calculation Formula:
CompHz = Freq. A × Freq. H + Freq. C
Example Calculation:
Model No.: E18CK
Operation Mode: Cooling
When Intake Air Temperature - Internal setting Temperature: 1.5°C
CompHz = Freq. A × Freq. H + Freq. C
=1.53 × 46 + 2.5
=72 Hz (It cuts down less than a decimal point)
Cooling & Soft Dry |
|
|
| E18CK |
| E21CK | ||||||
|
|
|
|
| Freq. A |
| Freq. C |
| Freq. A | Freq. C | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
Low Load (Freq. H | 9) | 1.2 |
| 5.0 | 1.7 |
| 7.0 | |||||
|
|
|
|
|
|
|
|
|
|
|
| |
High Load (Freq. H > 10) | 1.53 |
| 2.5 | 2.0 |
| 4.0 | ||||||
|
|
|
|
|
|
|
|
|
| |||
| Heating |
|
|
| E18CK |
| E21CK | |||||
|
|
|
|
| Freq. A | Freq. C | Freq. A | Freq. C | ||||
|
|
|
|
|
|
|
|
|
|
|
| |
Low Load (Freq. H | 11) |
| 1.6 |
| 8.0 |
| 1.9 |
| 7.0 | |||
|
|
|
|
|
|
|
|
|
|
| ||
High Load (Freq. H > 12) |
| 2.2 |
| 1.0 |
| 2.35 |
| 1.0 | ||||
|
|
|
|
|
|
|
| |||||
Freq. Range |
|
|
| E18CK |
| E21CK | ||||||
Cooling | Fc |
|
|
|
| 72 |
|
| 96 | |||
|
|
|
|
|
| |||||||
| Operation Range |
|
| 12 ~ 86 |
| 12 ~ 102 | ||||||
|
|
|
|
|
|
|
|
|
| |||
Heating | Fh |
|
|
|
| 86 |
|
| 92 | |||
| Operation Range |
|
| 14 ~ 128 |
| 14 ~ 128 | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Remarks:
When Freq. H is equal to 46 (Cooling), 39 (Heating) or above, the Comp. may run at the freq. higher than Fc or Fh up to max. freq. operation.
Best Amenity Control
Every 90s (Cooling), 120s (Heating) maintain same zone Freq. H + 1 until Fc (46), Fh (39).
8.1.3.Cooling Operation8.1.3.1.Thermostat control•Compressor is OFF when Intake Air Temperature - Internal Setting Temperature <
•Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF point +0.5°C.
17