3. Explanation of operation
1)Before the deice is started, compressor frequency is set to the specified value for
2)After deice is started, the
3)After
4)Before deice is ended, if the outdoor heat exchanger temperature exceeds a°C, set compressor frequency and expansion valve to the specified values.
5)When outdoor heat exchanger temperature exceeds b°C, or 10.5 minutes has passed since the
6)After the above 5) operation, if the specified time has passed, the deice operation ending signal will be produced. The comp. Hz is set to the specified value and at the same time outdoor fan motor ON signal is produced.
7)After T6 the deice ending signal is produced,
4.Deice operation judgement condition
When any of below a, b, c, d condition is satisfied, deice signal is produced.
a.Continuously, outdoor heat exchanger temperature < 3°C for 120 minutes and outdoor heat exchanger temperature <
b.Continuously, outdoor heat exchanger temperature < 3°C for 80 minutes and outdoor heat exchanger temperature < - 6°C for 3 minutes and outdoor air temperature >
c.Continuously, outdoor heat exchanger temperature < 3°C for 40 minutes and outdoor heat exchanger temperature < - 7°C and outdoor air temperature
d.Continuously, outdoor heat exchanger temperature < 3°C for 40 minutes and outdoor heat exchanger temperature < - 8°C for 3 minutes and outdoor air temperature <
However, the first deice will start only after minimum of 60 minutes in operation.
(2nd deice and onward shall follow above conditions)
B. Auto clean deice
1.Purpose
To improve heating
2.Control Content:
1). Auto deice is performed 15 min. before standby operation
2). When below deice conditions are fulfilled, auto clean deice operation will start.
3). After auto clean deice is completed, standby operation is performed as per load.
4). When deice conditions are not fulfilled, auto clean deice will not happen and will continue with standby operation.
41