How to use electronic circuit diagram

TIMER TABLE <INDOOR>

 

 

Test mode

Name

Time

(When test point

 

 

Short-circuited)

4 way valve abnormality

4 min.

24 sec.

 

 

 

Outdoor air temp. for Hz No. decision

30 min.

0 sec.

Anti-dew formation control

20 min.

0 sec.

 

 

 

Anti-freezing control

6 min.

0 sec.

Thermo OFF delay

3 min.

0 sec.

Low pressure control (gas leakage) compressor OFF time

3 min.

0 sec.

 

 

 

Time delay safety control

2 min. 58 sec.

0 sec.

 

20 sec.

 

 

 

 

Odour timer status shift time

90 sec.

0 sec.

 

20 sec.

 

 

120 sec.

 

 

 

 

Intake air temp. sampling time

2 min.

0 sec.

Self diagnosis display time

10 sec.

0 sec.

 

 

 

Auto mode judgement sampling time

20 sec.

0 sec.

24 hours Real Timer

1 hour

1 min.

Heating SSHi fan speed shift

120 min.

12 sec.

 

 

 

Cooling SHi fan speed shift

30 min.

3 sec.

Hot start forced completion

4 min.

0.4 sec.

 

 

 

Auto mode judgement interval

30 min.

3 sec.

After Hot start / Deice

2 min.

12 sec.

TIMER TABLE <OUTDOOR>

 

 

Test mode

Name

Time

(When test point

 

 

Short-circuited)

DC PEAK

30 sec.

3 sec.

 

 

 

 

120 min.

24 sec.

Deice detection

80 min.

16 sec.

 

 

 

 

40 min.

8 sec.

 

40 min.

8 sec.

Hz lock time

30 sec.

0 sec.

 

 

 

Outdoor fan delay operation control

30 sec.

3 sec.

4 way valve delay operation control

3 min.

18 sec.

 

 

 

97