1.When indoor heat exchanger temperature is lower than 2°C continuously for six minutes, compressor will stop operating.
2.Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 10°C.
3.At the same time, indoor fan speed increase +40 rpm compared to its normal operation.
4.If indoor heat exchanger temperature is higher than 10°C for five minutes, the fan speed will return to its normal operation.
8.2.2.4.a)Control 1
•During
•This control is cancelled after started for 420 minutes, or remote control setting temperature or fan speed setting is changed.
b)Control 2
•When the following conditions occurs for 20 minutes continuously,
1.Indoor intake air temperature is 25°C or above and less than 29°C.
2.Outdoor air temperature is less than 30°C.
3.Air vane control: Manual Horizontal Airflow and Manual Vertical Airflow.
4.Fan speed is quiet Lo.