Panasonic CU-4KE24NBU, CU-4KE31NBU, CU-3KE19NBU Air Purging with a Vacuum Pump for Test Run

Models: CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU

1 124
Download 124 pages 42.9 Kb
Page 115
Image 115
4. Air Purging

3-7. Taping the Tubes

After a tube has been insulated, CAUTION never try to bend it into a narrow curve, as this may cause the tube

to break or crack.

(1)At this time, the 2 refrigerant tubes (and electrical wire if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing.

(2)Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 18)

(3)Clamp the tubing bundle to wall, using 1 clamp approx. every 47" (120 cm).

NOTE

Do not wind the armoring tape too tightly, since this will decrease the heat insulation effect. Also, be sure the con- densation drain hose splits away from the bundle and drips clear of the unit and the tubing.

3-8. Finishing the Installation

After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 19)

Clamp

Insulated tubes

Fig. 18

Apply putty here

Tubing

Fig. 19

4. Air Purging

Service

Air and moisture remaining in the refrigerant system have valve on

undesirable effects as indicated below. Therefore, they

narrow

tube side

must be purged completely.

 

 pressure in the system rises

Service

valve on

 

 operating current rises

wide tube

side

 

 cooling efficiency drops

 

 moisture in the air may freeze and block capillary tubing

 water may lead to corrosion of parts in the refrigerant system

With push-pin

Air Purging with a Vacuum Pump (for Test Run)

D

Manifold gauge

C

(special for R410A)

Low-pressure

High-pressure valve

B

valve

 

Vacuum pump

A

 

 

adapter

Leave the Lo

Hi

(for preventing

 

valve open.

 

reverse flow)

 

 

(special for

 

Open

 

 

 

R410A)

 

 

 

 

Hex wrench

 

Vacuum

 

 

pump

 

Charging hose

 

 

 

 

 

(special for R410A)

 

Fig. 20

In order to protect the earth’s environment, be sure to use a vacuum pump to perform the air purge.

(Never perform an air purge by using the refrigerant gas cylinder or other external gas, or by using the gas inside the outdoor unit.)

CAUTION

In order to prevent charging errors with the air conditioner that uses R410A, the screw diameter at the service valve charging port has been changed. When recharging or performing other servicing, use the special charging hose and manifold gauge.

19

Page 115
Image 115
Panasonic CU-4KE24NBU, CU-4KE31NBU, CU-3KE19NBU service manual Air Purging with a Vacuum Pump for Test Run