Panasonic CU-4KE24NBU, CU-4KE31NBU, CU-3KE19NBU Wiring Instructions for the Outdoor Unit, Fig

Models: CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU

1 124
Download 124 pages 42.9 Kb
Page 121
Image 121
5-5. Wiring Instructions for the Outdoor Unit

5-5. Wiring Instructions for the Outdoor Unit

CAUTION

Be sure to correctly align inter-unit cables A, B, C and D.

Outdoor unit

Indoor unit A

 

 

 

 

Terminal board

 

 

 

 

 

 

 

 

 

1

2

1

2

3

4

5

6

7

8

9 10 11 12

Inter Unit

Inter Unit

(conduit)

(conduit)

Power supply (conduit)

Power: Single-phase, 230/208VAC 60HZ

Power breaker (not provided)

Manual backgroundManual background Ground Power cable (not provided) (#12: Less than 85 ft.)

Indoor unit D

A is the indoor unit with

 

 

 

 

refrigerant tubing that is

 

 

 

 

 

 

 

 

connected to service valve

1 2 3

 

A (bottom) of the outdoor unit.

 

 

 

 

 

 

 

 

 

Terminal board

 

 

 

 

 

 

 

D is the indoor unit with

 

 

 

refrigerant tubing that is

 

 

 

1 2 3

connected to service valve

 

 

 

D (top) of the outdoor unit.

Label A

Label D

Terminal board

 

A

D

 

Indoor unit B

Manual backgroundBManual background is the indoor unit with refrigerant tubing that is

connected to service valve B 1 2 3 (second from the bottom) of Manual backgroundManual background

the outdoor unit.

Terminal board

Inter-unit cables #14 (not provided)

Inter-unit cables #14 (not provided)

Label B

Manual backgroundManual backgroundBManual backgroundManual backgroundManual backgroundManual background

Inter-unit cables

Indoor unit C

#14 (not provided)

 

 

 

 

 

 

 

 

 

 

 

C is the indoor unit with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

refrigerant tubing that is

 

 

 

 

 

 

 

 

 

 

Inter-unit cables

 

 

1 2 3

connected to service valve

#14 (not provided)

 

 

 

 

 

C (third from the bottom)

 

 

 

 

 

of the outdoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

Label C

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal board

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Be sure to perform grounding. Manual background Attach a ground wire to either the

outdoor unit or indoor unit.

Manual background If there is a grounding terminal inside the room, use the grounding screw inside the indoor unit.

Manual background Be sure to apply the provided labels to both ends of the inter-unit cables to prevent mis- wiring. The units will not function if the wiring connections are incorrect.

# ... AWG (American Wire Gauge)

Fig. 31

Use a dedicated air conditioner circuit for power.

To make connections to the outdoor unit, remove the inspection panel and tubing panel.

Do not bring the inter-unit cables or power cable into contact with tubing or service valves.

Use outdoor unit cable fasteners and fasten the inter-unit cables at the location where the cables are double- sheathed.

Arrange the wiring so that the inter-unit cables are contained in the inspection panel and tubing panel, as shown in Fig. 31.

25

Page 121
Image 121
Panasonic CU-4KE24NBU, CU-4KE31NBU, CU-3KE19NBU service manual Wiring Instructions for the Outdoor Unit, Fig