7-2-3. Low Start Current
Operation starts at (8 Hz), and the start current is less than the normal operating current. This prevents the flickering of fluorescent lights or television screens that occurs when ordinary A/C units start.
7-2-4. Compressor Temperature Control
To protect the compressor coil from overheating, the operating frequency is controlled based on the compressor discharge temperature.
Compressor discharge temperature
(°F)
Trip
(230)
5Hz every 30 sec. reduction
(223)
2Hz every 30 sec. reduction
(212)
Increase
prohibit range
No control
(Hz reduction)
(194)
*Within the
7-2-5. Control at HEAT Start-up
If HEAT operation is started when the outdoor air temperature is 59 °F or below, the unit operates at the HEAT
Reset conditions
(1)The compressor frequency exceeds the
(2)The compressor thermostat is OFF.
(3)Frequency reduction for indoor
(4)The outdoor air temperature is above 59 °F.
(5)The