Page 51
Image 51
: CS-MKE12NB4U × 3

Outdoor Unit

: CU-3KE19NBU

 

 

 

 

 

 

 

 

Indoor Unit

: CS-MKE12NB4U × 3

 

 

 

 

 

 

 

Power Supply : 230V Single Phase 60Hz

 

 

 

 

 

 

 

 

< Cooling Capacity >

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RATING CAPACITY:

17,400 BTU/h

 

AIR FLOW RATE:

706 CFM

 

INDOOR

 

 

 

 

OUTDOOR

 

 

 

 

 

ENT. TEMP. o F ( o C)

 

 

AMBIENT TEMP. o F ( o C)

 

 

 

WB

 

DB

 

65

75

85

95

105

115

 

 

 

 

 

(18.3)

(23.9)

(29.4)

(35.0)

(40.6)

(46.1)

 

 

 

 

TC

17,460

16,880

16,260

15,760

15,020

14,220

 

 

72

(22.2)

SHC

15,450

15,180

14,900

14,630

14,350

13,940

 

59

76

(24.4)

SHC

17,460

16,880

16,260

15,760

15,020

14,220

 

(15.0)

80

(26.7)

SHC

17,460

16,880

16,260

15,760

15,020

14,220

 

 

84

(28.9)

SHC

17,460

16,880

16,260

15,760

15,020

14,220

 

 

88

(31.1)

SHC

17,460

16,880

16,260

15,760

15,020

14,220

 

 

 

 

TC

18,290

17,700

17,060

16,570

15,810

14,980

 

 

72

(22.2)

SHC

12,570

12,300

12,020

11,890

11,610

11,200

 

63

76

(24.4)

SHC

15,180

14,900

14,630

14,490

14,080

13,810

 

(17.2)

80

(26.7)

SHC

17,920

17,650

17,060

16,570

15,810

14,980

 

 

84

(28.9)

SHC

18,290

17,700

17,060

16,570

15,810

14,980

 

 

88

(31.1)

SHC

18,290

17,700

17,060

16,570

15,810

14,980

 

 

 

 

TC

19,120

18,520

17,870

#

17,400

16,620

15,760

 

 

72

(22.2)

SHC

9,690

9,420

9,140

9,000

8,730

8,460

 

67

76

(24.4)

SHC

12,300

12,020

11,750

11,610

11,340

11,060

 

(19.4)

80

(26.7)

SHC

15,040

14,770

14,490

14,350

14,080

13,670

 

 

84

(28.9)

SHC

17,650

17,370

17,100

16,960

16,620

15,760

 

 

88

(31.1)

SHC

19,120

18,520

17,870

17,400

16,620

15,760

 

 

 

 

TC

19,950

19,350

18,690

18,240

17,440

16,560

 

 

72

(22.2)

SHC

6,540

6,400

6,120

5,990

5,710

5,440

 

71

76

(24.4)

SHC

9,140

9,000

8,730

8,590

8,320

8,040

 

(21.7)

80

(26.7)

SHC

11,890

11,750

11,470

11,340

11,060

10,790

 

 

84

(28.9)

SHC

14,490

14,350

14,080

13,940

13,670

13,390

 

 

88

(31.1)

SHC

17,100

16,960

16,690

16,550

16,270

16,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

20,670

20,070

19,400

18,990

18,180

17,290

 

75

76

(24.4)

SHC

6,260

5,990

5,850

5,710

5,440

5,160

 

(23.9)

80

(26.7)

SHC

9,000

8,730

8,590

8,460

8,180

7,910

 

 

84

(28.9)

SHC

11,610

11,340

11,200

11,060

10,790

10,510

 

 

88

(31.1)

SHC

14,220

13,940

13,810

13,670

13,390

13,120

TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)

NOTE

1.Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB

:Outdoor Ambient Temp. 95 °F (35 °C) DB

2.Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.