Panasonic CU-4KE24NBU, CU-4KE31NBU Insulation of Refrigerant Tubing, Indoor unit, Outdoor unit

Models: CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU

1 124
Download 124 pages 42.9 Kb
Page 25
Image 25
Manual background

Outdoor Unit CU-4KE24NBU

Indoor unit

 

Outdoor unit

 

 

 

 

Service valve on

Sub

 

Main

Compressor

 

CW

 

 

wide tube

 

 

Wide tube

DW

accumulator

 

accumulator

 

O.D.1/2"

 

 

 

 

 

O.D.3/8"

 

 

High pressure

 

 

BW

 

 

switch

 

 

 

 

H.P.

 

O.D.3/8"

 

 

 

 

 

 

 

 

 

 

AW

 

 

 

 

O.D.3/8"

Header

4-way

 

 

 

 

 

 

 

 

valve

 

 

 

 

 

 

 

exchanger

 

 

Defrost valve for

S

 

 

 

 

 

hot gas bypass

 

 

 

 

 

 

 

 

 

Electric

 

 

 

 

Service valve on

expansion

 

 

Heat

 

valve

 

 

 

narrow tube

 

 

Narrow tube

DN

M

 

 

 

 

 

 

 

O.D.1/4"

 

M

 

 

 

 

CN

 

 

 

 

 

 

 

 

O.D.1/4"

 

M

 

 

 

 

BN

 

 

 

 

 

 

 

 

O.D.1/4"

 

M

 

 

 

 

AN

 

 

 

 

 

 

 

 

O.D.1/4"

Strainer

Header

 

 

 

 

 

 

 

Cooling cycle

Heating cycle

Defrosting cycle

Insulation of Refrigerant Tubing

IMPORTANT

Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min.5/16"(8 mm).

Thickness: Min.5/16"(8 mm)

Insulation

Thickness:

Min.5/16"(8 mm)

After a tube has been insulated, never try to bend it into a narrow

Wide tube

Narrow tube

CAUTION

curve because it can cause the tube to break or crack.

25

Page 25
Image 25
Panasonic CU-4KE24NBU, CU-4KE31NBU, CU-3KE19NBU service manual Insulation of Refrigerant Tubing, Indoor unit, Outdoor unit