CU-4KE31NBU, CU-4KE24NBU, CU-3KE19NBU service manual 1/f fluctuation fan, Fig
Models:
CU-3KE19NBU
CU-4KE24NBU
CU-4KE31NBU
1
75
124
124
Download
124 pages
42.9 Kb
72
73
74
75
76
77
78
79
<
>
Troubleshooting
Specification
Cooling Characteristics
Install
Refrigerant Flow Diagram
Dimension
WARNING When Wiring
Problems of Each Part and Inspection Points
Reset conditions
Diagnostic procedure
Page 75
Image 75
1/f fluctuation fan
250
200
150
(Step)
100
50
0
6-minute
cycle
Fig. 2
75
Page 74
Page 76
Page 75
Image 75
Page 74
Page 76
Contents
Pay special attention when servicing the unit
OUTDOOR UNIT : CU-3KE19NBU CU-4KE24NBU
CU-4KE31NBU
TECHNICAL & SERVICE MANUAL
SAFETY PRECAUTIONS
which may cause a unit breakdown
TROUBLESHOOTING BEFORE CALLING FOR SERVICE
Table of Contents
SPECIFICATIONS
REFRIGERANT FLOW DIAGRAM
SPECIAL PRECAUTIONS WHEN SERVICING UNIT
9. REFRIGERANT R410A
APPENDIX A
APPLICABLE INDOOR UNITS
Wall Mounted Type
Semi-ConcealedType
Outdoor Air Intake Temp
1. OPERATING RANGE
Temperature
Indoor Air Intake Temp
Number of Connectable Indoor Units
2. SPECIFICATIONS
2-1.Unit Specifications
Type
Voltage Rating
Type
Number of Connectable Indoor Units
Number of Operatable Indoor Units
Voltage Rating
Type
Number of Connectable Indoor Units
Number of Operatable Indoor Units
Voltage Rating
Type
Number of Connectable Indoor Units
Number of Operatable Indoor Units
Voltage Rating
Type
Number of Connectable Indoor Units
Number of Operatable Indoor Units
Voltage Rating
Type
Number of Connectable Indoor Units
Number of Operatable Indoor Units
Voltage Rating
Type
Number of Connectable Indoor Units
Number of Operatable Indoor Units
Voltage Rating
Type
Number of Connectable Indoor Units
Number of Operatable Indoor Units
Voltage Rating
Type
Number of Connectable Indoor Units
Number of Operatable Indoor Units
Compressor
2-2.Major Component Specifications
2-2-1.Outdoor Unit
Control PCB
Heat Exchanger Coil
Control PCB
Compressor
Fan Motor
Heat Exchanger Coil
Control PCB
Compressor
Fan Motor
Resistance k ohm
2-3.Other Component Specifications
Temperature F C
Temperature F C
Unit: inchmm 852-0-0010-11200-0
3. DIMENSIONAL DATA
Unit inchmm
Unit inchmm
4. REFRIGERANT FLOW DIAGRAM
4-1.Refrigerant Flow Diagram
Insulation of Refrigerant Tubing
Insulation of Refrigerant Tubing
Indoor unit
Outdoor unit
Insulation of Refrigerant Tubing
Indoor unit
Outdoor unit
5-1.Temperature Charts
5-1-1.Temperature Charts CU-3KE19NBU
5. PERFORMANCE DATA
Indoor Unit CS-MKE9NKU×
Cooling Characteristics
Heating Characteristics
Indoor Unit CS-MKE18NKU×
Indoor Unit CS-MKE9NB4U×
Indoor Unit CS-MKE12NB4U×
Heating Characteristics
Cooling Characteristics
Outdoor Unit CU-3KE19NBU
Indoor Unit CS-KE12NB4UW×
Indoor Unit CS-MKE7NKU×
5-1-2.Temperature Charts CU-4KE24NBU
current
Indoor Unit CS-MKE9NKU×
wideat
wideat
Indoor Unit CS-MKE12NKU×
Heating Characteristics
Cooling Characteristics
Outdoor Unit CU-4KE24NBU
1 High pressure performance chart
Cooling Characteristics
Heating Characteristics
1 Low pressure performance chart
Indoor Unit CS-MKE24NKU×
Indoor Unit CS-MKE9NB4U×
Indoor Unit CS-MKE12NB4U×
Heating Characteristics
Cooling Characteristics
Outdoor Unit CU-4KE24NBU
1 High pressure performance chart
Cooling Characteristics
Heating Characteristics
1 Low pressure performance chart
Indoor Unit CS-MKE7NKU×
5-1-3.Temperature Charts CU-4KE31NBU
Indoor Unit CS-MKE9NKU×
Indoor Unit CS-MKE12NKU×
Indoor Unit CS-MKE18NKU×
Indoor Unit CS-MKE24NKU×
1 High pressure performance chart
Cooling Characteristics
Heating Characteristics
1 Low pressure performance chart
Indoor Unit CS-MKE12NB4U×
temp
Indoor 70F
Indoor Unit CS-KE12NB4UW×
Indoor Unit : CS-MKE9NKU×
5-2.Cooling Capacity
Power Supply : 230V Single Phase 60Hz
Outdoor Unit : CU-3KE19NBU
CS-MKE12NB4U×
CU-3KE19NBU
CS-MKE9NKU×
CU-4KE24NBU
CS-KE18NB4UW+ CS-MKE12NB4U+ CS-MKE12NB4U
CU-4KE24NBU
CS-MKE9NKU×
CU-4KE31NBU
CS-MKE9NB4U×
CU-4KE31NBU
Indoor Unit CS-MKE9NKU×
5-3.Cooling Capacity Low Ambient
Power Supply : 230V Single Phase 60Hz
Outdoor Unit : CU-3KE19NBU
CS-MKE12NB4U×
CU-3KE19NBU
CS-MKE9NKU×
CU-4KE24NBU
CS-KE18NB4UW+ CS-MKE12NB4U+ CS-MKE12NB4U
CU-4KE24NBU
CS-MKE9NKU×
CU-4KE31NBU
CS-MKE9NB4U×
CU-4KE31NBU
Indoor Unit : CS-MKE9NKU×
5-4.Heating Capacity
Power Supply : 230V Single Phase 60Hz
Outdoor Unit : CU-3KE19NBU
CS-MKE12NB4U×
CU-3KE19NBU
CS-MKE9NKU×
CU-4KE24NBU
CS-KE18NB4UW+ CS-MKE12NB4U+ CS-MKE12NB4U
CU-4KE24NBU
CS-MKE9NKU×
CU-4KE31NBU
CS-MKE9NB4U×
CU-4KE31NBU
6. ELECTRICAL DATA
6-1.Electric Wiring Diagrams
Outdoor Unit CU-4KE24NBU 8FA2-5251-11500-1
Outdoor Unit CU-4KE31NBU 8FA2-5251-11300-1
7-1.Explanation of Functions
7. FUNCTIONS
Explanation
Clean defrost
Control/conditions
Unit operation
Control/conditions
Temperature of releasing
Fig.
Table
SENSOR
Control/conditions
Unit operation
Explanation
Fig.
1/f fluctuation fan
< Low Ambient Cooling Operation >
7-2-1.Defrost Detection and Release
7-2.Protective Functions
2 Current control
7-2-2.Current Control
Description of function
1Automatic frequency control
Reset conditions
7-2-4.Compressor Temperature Control
7-2-3.Low Start Current
7-2-5.Control at HEAT Start-up
8. TROUBLESHOOTING BEFORE CALLING FOR SERVICE
8-2.Trouble Diagnosis by Error Monitor Lamps
8-2-1.Location of the Error Monitor Lamps
8-2-2.Display of the Error Monitor Lamps
8-3.Checking the Outdoor System
8-3-1.Checking the outdoor unit
8-3-2.Checking the defrost operation
8-4.Trouble Diagnosis of Each Part
8-4-1.Problems of Each Part and Inspection Points
3 Compressor
8-4-2.Inspection Points for Each Part
1 Outdoor control circuit board
2 Fuse
7 Electric expansion valve
8 Branch tubing temperature sensor
9 Breaker
10 Refrigerant gas pressure
Remedy for symptom 3 to
8-5.Trouble Diagnosis of Fan Motor
Diagnostic procedure
Diagnostic results
9-1-3.Characteristics
SPECIAL PRECAUTIONS WHEN SERVICING UNIT
9-1.Characteristics of New Refrigerant R410A
9-1-1.What is New Refrigerant R410A?
No addition of compressor oil for R410A
9-2.Checklist before Servicing
Tubing precautions
Size of flare
9-3.Tools Specifically for R410A
9-4.Tubing Installation Procedures
9-5.In Case of Compressor Malfunction
9-5-1.Procedure for Replacing Compressor
Page
9-6.In Case Refrigerant is Leaking
9-8-1.Use of Existing Units
9-7-1.When Tubes are Extended
9-7.Charging Additional Refrigerant
9-8. Retro-FittingExisting Systems
Page
CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU
APPENDIX A INSTALLATION INSTRUCTIONS
For Outdoor Unit
Contents
When Transporting
SPECIAL PRECAUTIONS
In Case of Improper Installation
WARNING When Wiring
fins of the outdoor unit. You may get injured
When Servicing
Others
RQRWLQVWDOORQO\DVLQJOHLQGRRUXQLW
1. General
2. Installation Site Selection
Required Amount
Max. Allowable Total
Limit of
Limit of Elevation
3/89.52mm
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
CS-MKE24NKU
Outdoor unit
Indoor unit
5/815.88mm
About
Dimensions
Air Intake Baffle
Air Discharge Baffle
Dimensions
2. Air Discharge Baffle
3 Installation procedure
4 Precautions for installation
1. Air Intake Baffle
Fig. 6b
unit: inch mm
2-5.Outer Dimensions of Outdoor Unit
Fig. 6a
Indoor unit C Indoor unit B
2-6. Diagram of Outdoor Unit Installation
Indoor unit D
Indoor unit C Indoor unit B
3-1. Embedding the Tubing and Wiring
3. Installation Process
Fig.
D C B
3-4.Caution before Connecting Tubes Tightly
Fig.
3-6.Insulation of Refrigerant Tubing
Air Purging with a Vacuum Pump for Test Run
4. Air Purging
adapter manual, and use the adapter correctly
Fig.
Table
gas without releasing it into the atmosphere
Pump Down
Table
5. Wiring Instructions
5-1.General Precautions on Wiring
5-2.Recommended Wire Length and Diameter
Each wire must be firmly connected
5-4.How to Connect Wiring to the Terminal
Fig.
5-5.Wiring Instructions for the Outdoor Unit
Fig.
6. Test Run
Checking tubing and wiring
Performing a test run
8. Installation Check Sheet
7. Connecting a Home Automation Device
DC1111-0