3.2.9 Surge Protector Installation
CAUTION
Performing surge protection is essential. Make sure to follow the instructions in this section.

Overview

A massive electrical surge can be caused if lightning strikes a telephone cable 10 m (33 ft) above ground, or
if a telephone line comes into contact with a power line. A surge protector is a device that is connected to a
CO line to prevent potentially dangerous electrical surges from entering the building via the CO line and
damaging the PBX and connected equipment.
To protect the system from electrical surges, we strongly recommend connecting the system to a surge
protector that meets the following specifications:
Surge arrestor type: 3-electrode arrestor
DC spark-over voltage: 230 V
Maximum peak current: at least 10 kA
Additionally, proper grounding is very important for the protection of the system (refer to "3.2.3 Frame Ground
Connection").
Many countries/areas have regulations requiring surge protection. Be sure to comply with all applicable laws,
regulations, and guidelines.

Installation

CO Line CO LineCO Line
Ground
Surge
Protector
Extn.
Extn.
Extn.: Extension line
SLT
PT
PT-interface CS
CS
PBX
Frame
Ground
Terminal
Board
Document Version 2011-10 Installation Manual 57
3.2.9 Surge Protector Installation