Panduit PN380 manual Required Tools, Site and Equipment Preparation, Torque Settings

Models: PN380

1 20
Download 20 pages 58.74 Kb
Page 12
Image 12

PANDUIT DPoE Power System User’s Guide

Issue 1.0

 

Part Number: PN380

Table 5: Minimum Recommended DC AWG for 90° C Cabling for

 

Unprotected Outputs

 

 

 

 

 

Total Rectifier Current

Wire and Lug Gauge

 

 

Rating (A)

(AWG) using 90° C wire

 

 

 

(NEC Table 310.16)1

 

 

10

16

 

 

20

14

 

 

25

12

 

 

30

12

 

 

40

10

 

 

50

8

 

 

75

6

 

Torque Settings

The following table shows recommended torque settings for all mechanical and electrical connections according to screw or nut size in inch pounds (in-lbs).

Table 6: Recommended Torque Settings

Screw or Nut Size

Toque (in-lbs)

4-40

6

6-32

12

8-32

22

10-32

37

12-24

50

¼-20

65

Required Tools

The DPoE Power System is designed to be installed with a minimum number of commonly available tools:

#1 & #2 flat blade and Phillips head screwdrivers

Torque wrench

7/16” socket, ¼” drive

Wire and cable strippers (PANDUIT part number CT-100)

Wire and cable crimpers (such as PANDUIT part CT-1550, CT-1551, CT-1570, CT-1700 Contour CrimpTM Controlled Cycle Crimp Tools) (used for optional bulk DC connection)

Site and Equipment Preparation

Prior to unpacking the DPoE Power System, note any physical package damage that could indicate potential damage to the contents. After removing DPoE Power System from the boxes and packing material, inspect for shipping and/or other damage. Any problems should be reported to PANDUIT technical support.

1Table 310.16 uses Table 3B – Sizes of Conductors from BS EN 60950:2000, “Safety of Information Technology Equipment,” December 2000 for non-building wiring.