PANDUIT DPoE Power System User’s Guide | Issue 1.0 |
| Part Number: PN380 |
DC Output
DC connections are accomplished via the rear terminal blocks and bulk output connection as shown in Figure 9: Chassis (Rear View) - DC Connections.
The DPoE Power System Chassis allows a bulk DC connection as shown in Figure 9: Chassis (Rear View) - DC Connections. The bulk DC connection may be optionally used to ensure continued power to the connected DPoE Power Patch Panels and the PD connected to the panels in the event of a power failure. This connection may be used as a battery input or as an unfused bulk output. The bulk DC connection requires properly crimped terminal lugs (1/4” single hole lug with a max tongue width of 0.63” or less). Terminal lugs (such as PANDUIT part number
Size wires based on the total rectifier capacity and choose conductor size according to Table 5: Minimum Recommended DC AWG for 90° C Cabling for Unprotected Outputs . For battery or bulk DC connections, place lug on the corresponding positive and negative studs, and secure the connections with the included nuts.
Slot 14
Slot 1
SLOT
for NIC Card
Figure 8: Chassis (Front View) - GMT fuse holder
GMT fused return output connections
Positive Output or Battery Input
GMT fused negative
Negative Outputoutput connections or Battery Input
Figure 9: Chassis (Rear View) - DC Connections
10