Panduit PN380 manual Package Contents, Heat Dissipation, AC Input Wiring

Models: PN380

1 20
Download 20 pages 58.74 Kb
Page 8
Image 8

PANDUIT DPoE Power System User’s Guide

Issue 1.0

 

Part Number: PN380

Package Contents

The DPoE Power system chasses (PANDUIT part number DPoEPWRCM or DPoEPWRCU) are shipped with the following included items.

Table 2: Package Contents

Item

Quantity

Notes

DPoE Power System User’s Guide

1

This document. PANDUIT part number PN380

Cord Brackets

3

For securing the individual power cords to the rear

 

 

of the DPoE Power System Chassis

Screws with integrated washers

4

For securing the DPoE Power System chassis to

 

 

a 19” rack

Nuts

2

For securing the lugs to the bulk DC connection

 

 

on the rear of the DPoE Power System chassis

Screws with integrated washers

6

#4-40 screws for securing the cord brackets to the

 

 

back of the DPoE Power system chassis

 

 

 

CD-ROM

1

Element Management Software for the DPoE

 

 

Power System (included with DPoEPWRCM only)

 

 

 

NOTE:

GMT fuses, which are installed as part of installing the DPoE Power System, are NOT included with the shipment. Fuses can be ordered in packages of 10 from PANDUIT (part number DPoEPWRF10). Fuses are also available from Littelfuse® and Bussman®. Their part numbers are as follows:

Littelfuse® 481 series 10 Amp fuse; part number 0481010 Bussman® Fast-Acting Indicating fuse; part number GMT-10A

Heat Dissipation

The following table displays the maximum and typical British Thermal Units per hour (BTU/hr) of heat dissipated from each rectifier. The maximum is calculated at 90 VAC, and typical is calculated at 230 VAC.

Table 3: Heat Dissipation

Part Number

Typical BTU/hr

Max BTU/hr

DPoEPWRR500

249

410

DPoEPWRR1250

451

833

AC Input Wiring

The DPoE Power System chassis uses an individual AC feed architecture (See Figure 1: Individual AC Feed Wiring Architecture), which requires one AC feed per rectifier. The, up to three, AC connections are made using the IEC320 receptacles on the rear of the chassis (See Figure 6: Chassis (Rear View) - AC Connections).

Connect each feed, using the appropriate power cord as listed in Table 1: DPoE Power Components Available into the appropriate receptacle on the back of the system. Cord securing brackets are included to secure the AC plugs to the chassis (See Figure 7: Securing Cord Bracket to Chassis).

3

Page 8
Image 8
Panduit PN380 manual Package Contents, Heat Dissipation, AC Input Wiring