TESTING GAS PRESSURE

Section III. Installation

13

 

 

TESTING GAS PRESSURE

1.Push the power switch to “OFF”.

2.Turn the gas valve knob to “OFF”.

3.Remove 1/8 in. NPT plug on the outlet side of the valve and screw in the fitting from the Manometer kit.

4.Connect the Manometer hose to the fitting.

5.Turn the gas valve knob to “ON”.

6.Turn on the heater and read the Manometer.

7.The Manometer must read per the values of the Gas Pressure Requirement Table, on manifold side of the gas valve, while operating.

8.If reading is below specified; check the inlet pressure while the heater is running to make sure of proper supply before attempting adjustments.

InletManifold

MiniMax NT LN

Illustration above is for Natural Gas, see Table 5.

9.For adjustment, remove the Regulator Adjustment

Cap and using a screwdriver turn the screw clockwise to increase - counterclockwise to decrease gas pressure.

GAS PRESSURE REQUIREMENTSCAUTION

The use of Flexible Connectors (FLEX) is NOT recommended as they cause excessive high gas pressure drops.

GAS PRESSURE REQUIREMENTS

Regulator Adjustment Cap

1/8" NPT Plug

(Inlet Press)

 

ON

 

OFF

 

1/8" NPT Plug

Figure 4.

(Manifold Press)

 

 

Natural

Gas Pressure

Model

 

Inches

 

 

 

 

W.C.

 

 

 

Maximum Inlet

LN

10

 

 

 

Minimum Inlet

LN

5*

 

 

 

Manifold

LN

4

 

 

 

NOTE: All readings must be taken while heater is operating. Any adjustments or readings made while heater is off will result in performance problems.

All Values are +/- 0.2 inch W.C. * 6 inch. W.C. for LN 400 Model.

Table 5.

Rev. E 4-19-05

P/N 472089

Page 13