Polaris PC 150-50 2NV Water Piping System, Gas Input Rate, Piping Installation, Input Graph

Models: PC 150-50 2NV PC 130-50 2NV PC 100-34 2NV PC 199-50 3NV PC 130-34 2NV PC 150-34 2NV PC 175-50 3NV

1 64
Download 64 pages 41.68 Kb
Page 13
Image 13
Gas Input Rate

Gas Input Rate

The gas input rate of this water heater is affected by several environmental factors such as:

The heating value of the gas

The air and gas densities (which vary widely due to baro- metric pressure and temperature changes)

Venting installations (pipe diameter, length and fittings)

Altitude

When measuring the input rate these factors should be incorporated into the calculations. Also measure the gas consumption over a sufficiently long time to obtain an accurate gas consumption rate (e.g. 3-5 minutes, not one revolution of the meter needle).

Long vents and each additional elbow, inherently reduce the gas input rate due to increased resistance to moving combustion air and flue gases. The approximate maximum/ minimum input for the 100k, 130k, and 150k models is shown in figure 14.

Figure 14: Input Graph

WATER PIPING SYSTEM

Piping Installation

Piping, fittings, and valves should be installed according to the installation drawing (figure 15). If the indoor installation area is subject to freezing temperatures, the water piping must be protected by insulation.

The water supply pressure should not exceed 80 psi

(551.5 kPa). If this occurs, a pressure reducing valve with a bypass should be installed in the cold water inlet line. This should be placed on the supply to the entire house in order to maintain equal hot and cold water pressures.

Important: Heat cannot be applied to the water fittings on the heater as they may contain nonmetallic parts. If solder connections are used, solder the pipe to the adapter before attaching the adapter to the hot and cold water fittings.

Important: Do not install this water heater with iron or galvanized piping. Use brass caps on all unused inlet/ outlet connections.

1.Install the water piping and fittings as shown in figure 15. Note: If state or local codes require, install a vacu- um relief valve per the manufactures instructions in the cold water supply line. Connect the cold water supply (use 1” NPT) to the fitting marked “COLD INLET”.

Do not turn the cold water nipple. The mark should remain along the top side of the nipple. Connect the hot water supply (use 1” NPT) to the fitting marked “HOT OUTLET”.

2.Always use a suitable grade of joint compound and be certain that all fittings are tightened properly.

3.The installation of unions in both the hot and cold water supply lines is recommended for ease of removing the water heater for service or replacement.

4.If installing the water heater in a closed water system, install an expansion tank in the cold water line as speci- fied under “Closed System/Thermal Expansion” (Page 14).

5.Install a shut-off valve in the cold water inlet line. It should be located close to the water heater and be easily accessible. Know the location of this valve and how to shut off the water to the heater.

6.The Polaris® gas water heater is shipped with a factory- installed Temperature and Pressure Relief Valve. Install a discharge line in the opening in the T & P valve (see instructions on Page 16).

7.After piping has been properly connected to the water heater, remove the aerator at the nearest hot water faucet. Open the hot water faucet and allow the tank to completely fill with water. (To prevent damage to the unit, DO NOT connect power until the tank is COMPLETELY FILLED). To purge the lines of any excess air, keep the hot water faucet open for 3 min- utes after a constant flow of water is obtained. Close the faucet and check all connections for leaks.

Corrosion and Water Quality

Water quality will vary from location to location and may contain contaminates that may reduce the life or perfor- mance of the water heater. To test for contaminates a water quality test kit is available, reference part number 6903791.

Contaminates which can reduce the life or performance of the water heater if present in high quantities include those which contribute to hardness (dissolved minerals such as sodium, calcium and magnesium); plus chlorides and sulfates. Additionally, water that is too acidic or basic (measured as pH) can reduce the life of the water heater. Water treatment systems (such as water softeners for hardness) should be used and maintained properly if the contaminate levels exceed the following:

Warranty is void in applications which exceed the water quality requirements listed below.

Table 2:

 

Total Hardness:

12 grains per gal. (205 mg/liter) max.

Chloride:

200 mg/liter max.

pH:

6.5-8.0

Alkalinity:

200 mg/liter max.

13

Page 13
Image 13
Polaris PC 150-50 2NV Water Piping System, Gas Input Rate, Piping Installation, Corrosion and Water Quality, Input Graph