TROUBLESHOOTING

TROUBLESHOOTING

Table 5:

Ignition Control Module (ICM) LED Error Codes: (Flashes visible through viewport in access door)

FLASHES

INDICATED PROBLEM

CONTROL REACTION

1

Pressure Switch Closed

SC*

2

Pressure Switch Open

SL

3

Failed Ignition

SL3

4

Gas Valve Hardware Fault

SL

5

Flame Sense Hardware Fault

SC

6

False Flame

SL**

8

Ignition Control Hardware Fault

SL

9

Ignition Control Software Fault

SL

Rapid

L1 Polarity Detection

SC

SL (Soft Lockout): Control Automatically resets after 60 minutes.

SL3 (Soft Lockout/Hard Lockout): Control automatically resets after 60 minutes, with a maximum of 3 resets, followed by hard lockout requiring service.

SC (Self Clearing): Control will function normally as soon as it no longer detects the previously indicated fault.

*when pressure switch or blower relay opens

**when flame is no longer sensed.

† Blower Isolation Relay is used on models 150,000 BTU/Hr and above.

Note: If unit goes into a soft or hard lock-out the ignition control module can be reset by cycling power to the water heater.