Communication
Communications Mode Reference Chart
The following chart defines the UPS serial port contacts. Serial communication is not available with 3Com and AS/400 network configurations. Use only the applicable pins for the selected communication mode; otherwise, interference problems may occur.
Communication Mode | Function | Signal Name | Pin No. | True Condition | |
Serial | Data to UPS | RS232 TxD | 2 | N/A | |
|
|
|
|
| |
| Data from UPS | RS232 RxD | 3 | N/A | |
|
|
|
|
| |
| Signal Ground |
| 7 |
| |
|
|
|
|
| |
Novell | Battery On | ON.AC | 14/16 | Open | |
(Default) |
|
|
|
| |
Low Battery | TWO.MIN | 23/24 | Closed | ||
| |||||
|
|
|
|
| |
| Signal Ground |
| 7/15/25 |
| |
|
|
|
|
| |
Novell | Battery On | ON.AC | 14/16 | Closed | |
(Custom) |
|
|
|
| |
Low Battery | TWO.MIN | 23/24 | Closed | ||
| |||||
|
|
|
|
| |
| Signal Ground |
| 7/15/25 |
| |
|
|
|
|
| |
3Com | Shutdown (Remote) | SHUT.DOWN | 2 | Positive Voltage | |
(Default) |
|
|
|
| |
Low Battery | LOW.BATT | 9 | Positive Voltage | ||
| |||||
|
|
|
|
| |
| Battery On | PWR.FAIL | 10 | Positive Voltage | |
|
|
|
|
| |
| Signal Ground |
| 7 |
| |
|
|
|
|
| |
AS/400 | UPS Available | UPS Available | 11/13 | Closed | |
|
|
|
|
| |
| Battery On | Utility Failure | 14/16 | Closed | |
|
|
|
|
| |
| Bypass | UPS Offline | 17/19 | Closed | |
|
|
|
|
| |
| Low Battery | Low Battery | 23/24 | Closed | |
|
|
|
|
| |
| Signal Ground |
| 12/15/18/25 |
| |
|
|
|
|
|
NOTE Pin numbers separated by a forward slash ( / ) are connected together internally.