
Troubleshooting
Condition | Possible Cause | Action |
| UPS internal temperature is too | Shut down the UPS. Clear vents. Remove |
| high. The alarm beeps and the | any heat sources. Wait approximately |
OVERTEMP | UPS switches to Bypass mode | 5 minutes and retry. |
| for approximately 10 minutes, | Contact your service representative if |
| allowing the UPS to cool down. | condition persists. |
| Weak battery while in Normal | Allow the battery to charge for 24 hours, |
| mode. The alarm beeps. | then retest. Have batteries replaced if |
|
| condition persists. |
BATTERY | Battery breaker is open (O). | Verify that the battery circuit breaker is in |
| ||
|
| the ON ( ) position. |
| Battery cabinet is not properly | Verify that the battery cords are |
| connected to the UPS. | connected. |
| Weak battery while in Bypass | This usually indicates that the batteries |
| mode. | need replacing or the UPS requires service. |
|
| Contact your service representative. |
BATTERY
Self Test failure. UPS internal problem.
SELF TEST
The UPS may switch to Bypass mode, depending on the circumstances.
Reset the UPS by pressing the Output On button until the alarm beeps.
Contact your service representative if condition persists.
Resetting the UPS
To reset the UPS while an alarm condition is present, press the
Output On button until the UPS alarm beeps.
Silencing the Alarm
To silence the alarm for an existing fault, press and hold the Output On button for one second. The alarm becomes quiet.
If UPS status changes, the alarm beeps, overriding previous alarm silencing. Press the Output On button again to silence the alarm.
Powerware® 9 Prestige Series User’s Guide (600 VA - 1800 VA) : www.powerware.com | 59 |