Appendix

DIP Switch Description

DIP switch definitions for both types of the ConnectUPS Web/SNMP Cards are listed in Table 4.

Table 4. DIP Switch Modes

SW1

SW2

Description

 

 

 

Off

Off

Operational Mode (default)

 

 

 

Off

On

BOOTP/DHCP Enable Mode (overrides the serial/Telnet

 

 

configuration)

 

 

 

On

Off

Reserved

 

 

 

On

On

Reserved

 

 

 

Jumper 1 (JP1) Settings

The JP1 jumper is found on both the ConnectUPS-X and ConnectUPS-BD. The JP1 pins are NOT jumpered by factory-default. Table 5 shows the jumper definitions.

Table 5. JP1 Definitions

Jumper Setting Definition

1 and 2 Allows admin to be entered as the password when the programmed Superuser password has been forgotten

3 and 4 Disables all changes to the card’s configuration

NOTE On the ConnectUPS-BD, jumper positions 5 and 6, 7 and 8 are undefined; DO NOT jumper these positions.

32