Local Configuration

4.Turn on the UPS.

After a few seconds the PC displays a message indicating that the adapter is ready.

5.Press [Enter]. The Password screen appears (see Figure 6). If the Password screen does not appear, press [Enter] again.

If you still do not see the Password screen, check the following conditions:

:The communication settings of the terminal should be 9600 baud, No parity, 8 bits, and 1 stop bit.

:If the serial configuration is correct, check the cabling to verify all connections are secure.

:Verify that your terminal program is on the correct communication port for the serial connection.

:Verify that the UPS has input power and is turned on.

6.Type your password (the default password is admin) and press [Enter]. The Main Menu screen appears.

+============================================================================+

[ BestLink SNMP/WEB Adapter Configuration Utility ] +============================================================================+

Enter Password: *****

+============================================================================+

[ BestLink SNMP/WEB Adapter Configuration Utility ] +============================================================================+

1.SNMP/WEB Card Settings

2.Reset Configuration to default

3.Restart SNMP/WEB Card

0. Exit

Please Enter Your Choice =>_

Figure 6. BestLink SNMP/WEB Adapter Main Menu Screen

BestLink SNMP/WEB Adapter User’s Guide : LTM-1343 B Draft 10/03/2001