Local Configuration
5.Type 0 to exit the BestLink Adapter configuration. The BestLink Adapter automatically reboots and saves all settings after exiting the configuration function (see Figure 8).
NOTE The BestLink Adapter may take up to two minutes to reboot. Please wait before attempting communication with the adapter from a web browser or NMS.
NOTE Telnet Operation – Once the adapter is reachable on the network, you can use a telnet utility to adjust any of the configuration settings. The menus are identical to those seen during serial configuration and are
NOTE For an Internal BestLink Adapter – In a FERRUPS 0800, Axxium Pro, or Powerware 9170 UPS, you MUST change the Config BestDock parameter for that UPS back to NO or UPS as applicable. Refer to the UPS user’s guide for detailed instructions on changing the parameter through the UPS front panel configuration menu.
+============================================================================+
[ BestLink SNMP/WEB Adapter Configuration Utility ] +============================================================================+
1.Set the IP Address, Gateway Address and MIB System Group
2.Set SNMP/WEB Card Control Group
3.Set Write Access Managers
4.Set Trap Receivers
5.Set IP Addresses of Primary and Secondary Date Server
6.UPS Event Actions
7.Set UPS information
8.Set Superuser Name and Password
9.Email Notification
0.Back to Main Menu
Please Enter Your Choice =>0
+============================================================================+
[ BestLink SNMP/WEB Adapter Configuration Utility ] +============================================================================+
1.SNMP/WEB Card Settings
2.Reset Configuration to default
3.Restart SNMP/WEB Card
0. Exit
Please Enter Your Choice =>0
Figure 8. Exiting the Configuration Program
BestLink SNMP/WEB Adapter User’s Guide : | 11 |