Alarm or Condition

Possible Cause

Action

 

The UPS is running on

Correct the input voltage, if possible. The

 

battery power because the

UPS continues to operate on battery until

 

input voltage is too high or

the conditions is corrected or the battery is

 

too low.

completely discharged.

 

 

 

If the condition persists, the input voltage in

 

 

your area may differ from the UPS nominal.

 

The utility line voltage and

Have a qualified electrician check the

 

frequency are out of

wiring.

 

 

 

specification.

 

 

 

1 beep every 5

The battery may be fully

Plug the UPS into a power outlet for 24

seconds.

discharged.

hours to charge the battery. After charging

 

 

the battery, press and hold the

button

 

 

for 3 seconds; then check the

 

 

 

indicator.

 

 

 

 

If the

indicator is still on, see "UPS

 

 

Maintenance" to replace the battery.

 

 

The battery is not

Check the battery connections. Call your

 

connected correctly.

service representative if the problem

 

 

 

persists.

 

 

 

Ground wire connection

Have a qualified electrician correct the

 

does not exist or the line

wiring.

 

 

 

and neutral wires are

 

 

 

 

reversed in the wall outlet.

 

 

 

 

Power requirements exceed

Turn off and unplug the UPS. Remove some

100%

UPS capacity (101–110% for

of the equipment from the UPS. Wait at

 

3 minutes or 111–150% for

least 5 seconds until all LEDs are off and

 

10 cycles) or the load is

restart the UPS. You may need to obtain a

25%

defective.

larger capacity UPS.

 

 

 

 

UPS fault condition.

Save your work and turn off your

 

 

 

equipment. Turn off and unplug the UPS.

 

 

Contact your service representative. The

 

 

alarm cannot be silenced.

 

22

1000 - 2000 VA

1019297

 

User’s Manual

Revision A

Page 22
Image 22
Powerware UPS 1000 - 2200 user manual 100%