Operating Temperature |
|
| 10°C to 40°C |
|
|
| ||||||
|
|
| Optimal battery performance: 25°C |
| ||||||||
Storage Temperature |
|
|
| 0°C to 25°C |
|
|
| |||||
Transit Temperature |
|
|
|
|
| |||||||
Relative Humidity |
|
|
| |||||||||
Operating Altitude | Up to 3,000 meters above sea level |
| ||||||||||
Transit Altitude | Up to 15,000 meters above sea level |
| ||||||||||
Audible Noise | Less than 40 dBA Normal mode, typical load |
| ||||||||||
Less than 55 dBA Battery mode |
| |||||||||||
|
|
|
| |||||||||
Surge Suppression | ANSI C62.41 Category B (formerly IEEE 587), IEC | |||||||||||
|
|
| UL 1778, UL 497A (data line only); |
| ||||||||
Safety Conformance |
|
| CAN/CSA C22.2, No. 107.1; |
| ||||||||
|
|
|
| EN |
| |||||||
Agency Markings | UL and cUL; CE, |
| ||||||||||
EMC |
|
| EN |
| ||||||||
Table 7. Environmental and Safety |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| ||||||
Configuration | 1000 VA: (2) 24V, 9 Ah internal batteries |
|
|
| ||||||||
1500 VA: (4) 48V, 7 Ah internal batteries |
|
|
| |||||||||
|
|
|
|
|
| |||||||
|
|
| 2200 VA: (4) 48V, 12 Ah internal batteries |
|
|
| ||||||
|
|
|
|
|
| |||||||
EBM Configuration | PW5125 | (8) 24V, 9 Ah batteries |
|
|
| |||||||
|
|
| PW5125 | (8) 48V, 9 Ah batteries |
|
|
| |||||
|
|
|
|
| ||||||||
Type |
|
| Sealed, |
| ||||||||
|
|
|
| |||||||||
|
|
| Internal battery: less than 3 hours to 90% usable capacity at | |||||||||
|
|
| nominal line voltage after full load discharge |
| ||||||||
Charging | External battery: recharging at 80% load or less is |
| ||||||||||
recommended; no more than 16x discharge time to 90% usable | ||||||||||||
|
|
| ||||||||||
|
|
| capacity at nominal line voltage after full load discharge; an | |||||||||
|
|
| external battery charger is recommended for faster recharge | |||||||||
|
|
| times when using more than 2 EBMs. |
|
|
| ||||||
|
| |||||||||||
Monitoring | Advanced monitoring for earlier failure detection and warning; | |||||||||||
|
|
| auto detection of additional EBMs |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
| |||
Table 8. Battery |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |
Model |
| Internal UPS Batteries |
| 1 EBM |
| 2 EBMs |
| 3 EBMs |
| 4 EBMs | ||
|
|
|
|
|
|
|
|
|
|
| ||
1000 VA |
| 5/14 |
| 45/60 |
| 95/170 |
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| ||
1500 VA |
| 6/17 |
| 33/79 |
| 63/146 |
| 92/174 |
| 120/201 | ||
|
|
|
|
|
|
|
|
|
|
| ||
2200 VA |
| 6/14 |
| 26/60 |
| 55/170 |
| 81/198 |
| 106/224 | ||
|
|
|
|
|
|
|
| |||||
NOTE | Battery times are approximate and vary depending on the load configuration and | |||||||||||
battery charge. |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| ||||
Table 9. Battery Run Times (in Minutes at Full/Half Load) |
|
|
|
24 | 1000 - 2000 VA | 1019297 |
| User’s Manual | Revision A |