C. Installing Chimney Components

2100 Millennium Wood Stove (ACC)

R

Solid Pack Chimney with Metal Supports as a Thimble (Cont’d)

C. Installing Chimney Components

Chimney Connector

Single wall connector or stove pipe.

Min. Chimney Clearance to

Wall Spacer and

Combustibles - 2 inch (51mm)

Chimney Flue

Liner

FireclayChimney Height / Rise and Run

Liner or

Equivalent

Masonry Chimney Constructed to NFPA 211

Min. Clearance 2 inch (51mm)

1 inch (25mm) Air Space to Chimney Section

Chimney

Connector

Manual background Chimney Section

Trim Collar

Wall Band

Wall Spacer

This must be at least 24 gauge mild steel or 26 gauge blue steel. The sections must be attached to the appliance and to each other with the crimped (male) end pointing toward the stove. All joints, including the connection at the flue collar, should be secured with 3 sheet metal screws. Make sure to follow the minimum clearances to combustibles. Where passage through the wall, or partition of combustible con- struction is desired in Canada, the installation shall conform to CAN/CSA-B365.

Factory-built listed chimney connector (vented).

A listed connector (vented) must be used when installing this unit in a mobile home. The listed connectors must conform to each other to ensure a proper fit and seal.

Figure 16.1

Chimney Height / Rise and Run

This product was designed for and tested on a 6 inch (152mm) chimney, 14 to 16 feet (420-480cm) high, (includes stove height) measured from the base of the appliance. The further your stack height or diameter varies from this configuration, the possibility of performance problems exists.

Chimney height may need to be increased by 2 - 3% per each 1000 feet above sea level. It is not recommended to use offsets or elbows at altitudes above 4000 feet above sea level or when there are other factors that affect flue draft.

Crimped

Flue Gas

End

Direction

Toward

 

Stove

 

Secure pipe sections with a

minimum of 3 screws

Figure 16.2 Chimney Connector (Stove Pipe)

Manual background WARNING

Fire Risk.

Inspection of Chimney:

Chimney must be in good condition.

Meets minimum standard of NFPA 211

Factory-built chimney must be 6 inch (152mm) UL103 HT.

Manual background WARNING

Asphyxiation Risk.

DO NOT CONNECT THIS UNIT TO A CHIM- NEY FLUE SERVICING ANOTHER APPLI- ANCE.

DO NOT CONNECT TO ANY AIR DISTRI- BUTION DUCT OR SYSTEM.

May allow flue gases to enter the house.

Manual background WARNING

Fire Risk.

Follow Chimney Connector Manufacturer’s

Instructions for Proper Installation.

ONLY use connector:

Within the room, between appliance and ceiling or wall. Connector shall NOT pass through:

Attic or roof space

Closet or similar concealed space

Floor or ceiling

Maintain minimum clearances to combustibles

Manual background WARNING

Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to the owner’s information manual provided with this appli- ance. For assistance or additional information consult a qualified installer, service agency or your dealer.