2100 Millennium Wood Stove (ACC)

D. Chimney Termination Requirements

Follow manufacturer’s instructions for clearance, securing flashing and terminating the chimney.

Must have an approved and listed cap

Must not be located where it will become plugged by snow or other material

Must terminate at least 3 feet (91cm) above the roof and at least 2 feet (61cm) above any portion of the roof within 10 feet (305cm).

Must be located away from trees or other struc- tures

NOTE:

Chimney performance may vary.

Trees, buildings, roof lines and wind conditions affect performance.

Chimney height may need adjustment if smoking or overdraft occurs.

E. 2-10-3 Rule

These are safety requirements and are not meant to assure proper flue draft.

Less than 10 ft. (305cm)

2 ft. (61cm)

10 ft. (305cm) To Nearest Roofline

3 ft. (91cm)

Minimum

2 ft. (61cm)

3 ft. (91cm)

 

Minimum

Pitched Roof

Figure 17.1

10 ft. (305cm) or more

Less than 10 ft. (305cm)

 

 

Wall or Parapet

2 ft. (61cm)Minimum

3 ft. (91cm) Minimum

3 ft. (91cm) Minimum

 

Figure 17.2

Flat Roof

 

May 5, 2011

7039-131H

Page 17