Quadra-Fire 7008-115 owner manual F. Installing Adaptor and Termination Cap, Masonry, Or

Models: 7008-115

1 43
Download 43 pages 10.74 Kb
Page 21
Image 21
F. Installing Adaptor and Termination Cap

F. Installing Adaptor and Termination Cap

For installation of termination cap see minimum vent heights for various pitched roofs (see Figure 8.4) .

To install adaptor see Figure 8.5.

HORIZONTAL

OVERHANG

CAUTION! Risk of Cuts/Abrasions/Flying Debris.

Wear protective gloves and safety glasses during instal- lation. Sheet metal edges are sharp.

Damper Flashing Kit (Optional)

For use with LINK-DV4-30B Liner Kit.

Note: Damper may have to be removed to use this kit.

Run flex liners through 3 in. holes in damper flashing.

Attach damper flashing to firebox roof with self tapping

2FT.

MIN.

GAS DIRECT VENT

TERMINATION CAP

20 INCHES MIN.

VERTICAL

LOWEST

WALL

 

DISCHARGE

 

OPENING

 

X

12

Damper Flashing Kit (Optional) ROOF PITCH

IS X/ 12

H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING

screws included in kit.

CLASS A PIPE

Roof Pitch

H (Min.) Ft.

Flat to 6/12

....................

1.0*

Over 6/12 to 7/12

1.25*

Over 7/12 to 8/12

1.5*

Over 8/12 to 9/12

2.0*

Over 9/12 to 10/12

2.5*

Over 10/12 to 11/12

3.25

Roof Pitch

H (Min.) Ft.

Over 11/12 to 12/12

4.0

Over 12/12 to 14/12

5.0

Over 14/12 to 16/12

6.0

Over 16/12 to 18/12

7.0

Over 18/12 to 20/12

7.5

Over 20/12 to 21/12

8.0

Figure 8.5

* 3 foot minimum in snow regions

Figure 8.4 Minimum Height from Roof to Lowest Discharge Opening

To prevent odors and cold drafts, the chimney must be sealed around the vent with non-combustible blanket insulation or field fabricated metal plates.

Note: The LINK-DV4-30B

system REQUIRES this insulation.

Masonry

EXHAUST

AIR

VENT PIPE

Figure 8.6

LINK-DV30B

LINK-DV4-30B

Installation

Installation

TERMINATION

CAP

OR

SEAL GAP

AROUND FLEX PIPE

WARNING:

DO NOT BLOCK

THIS PIPE END!

Note: Untwist the pipe while extending it, to achieve full 30’ length.

Masonry INLET AIR

VENT PIPE

Factory Built

Wood Burning

OPTIONAL LINK-ZC-ADPB

FOR USE WITH CLASS A

WOODBURNING PIPE

Remove 18 inch x 18 inch flashing on cap by removing 3 screws. Connect both the LINK-ZC-ADPB to Class A Pipe and the termination cap to the LINK-ZC-ADPB with the self tapping screws provided.

Quadra-FireHUDBAY-INS7008-115 Rev. o • 8/11

21

Page 21
Image 21
Quadra-Fire 7008-115 owner manual F. Installing Adaptor and Termination Cap, Masonry, Factory Built Wood Burning, Or