5 Troubleshooting

With proper installation, operation, and maintenance your gas fireplace will

provide years of trouble-free service. If you do experience a problem, this

troubleshooting guide will assist a qualified service person in the diagnosis

of a problem and the corrective action to be taken. This troubleshooting

guide can only be used by a qualified service technician.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Symptom

Possible Cause

 

Corrective Action

1. After repeated

a. Defective ignitor.

 

Check the spark at the electrode and pilot. If no spark and electrode wire is

triggering of the red

 

 

properly connected, replace the ignitor.

or black piezo button,

 

 

 

b. Defective pilot or

 

Using match, light the pilot. If the pilot lights, turn off the pilot and trigger the red or

the spark ignitor will

 

misaligned electrode

 

black piezo button again. If the pilot lights, an improper gas/air mixture caused the

not light the pilot.

 

(spark at electrode).

 

bad lighting and a longer purge period is recommended. If the pilot will not light,

 

 

 

 

 

 

 

ensure the the gap at the electrode and pilot is one-eighth (1/8) inch to have a

 

 

 

 

strong spark. If the gap is OK, replace the pilot.

 

 

c. No gas or low gas

 

Check the remote shut-off valvess from the fireplace. Usually, there is a valve near

 

 

pressure.

 

the gas main. There can be more than one (1) valve between the fireplace and the

 

 

 

 

main.

 

 

d. No LP in tank.

 

Check the LP (propane) tank. You may be out of fuel.

2. The pilot will not

a. Defective

 

Check that the pilot flame impinges on the thermocouple. Clean and/or adjust the

stay lit after carefully

thermocouple.

 

pilot for maximum flame impingement.

following the lighting

 

 

 

instructions.

 

 

Ensure that the thermocouple connection at the gas valve is fully inserted and tight

 

 

 

 

(hand tighten plus 1/4 turn).

 

 

 

 

Disconnect the thermocouple from the valve, place one millivolt meter lead wire on

 

 

 

 

the tip of the thermcouple and the other meter lead wire on the thermocouple

 

 

 

 

copper lead. Start the pilot and hold the valve knob in. If the millivolt reading is less

 

 

 

 

than 15mV, replace the thermocouple.

 

 

b. Defective valve.

 

If the thermocouple is producing more than 15 millivolts, replace faulty valve.

 

 

 

 

 

3. The pilot is

a. ON/OFF switch or

 

Check the ON/OFF switch and wires for proper connections. Place the jumper

burning, there is no

wires defective.

 

wires across the terminals at the switch. If the burner comes on, replace the

gas burner, the valve

 

 

defective switch. If the switch is OK, place the jumper wires across the switch wires

knob is in the ON

 

 

at the gas valve. If the burner comes on, the wires are faulty or connections are

position, and the

 

 

bad.

ON/OFF switch is in

 

 

 

b. Thermopile may

 

If the pilot flame is not close enough physically to the thermopile, adjust the pilot

the ON position.

 

not be generating

 

flame.

 

 

 

 

 

sufficient millivoltage.

 

Be sure the wire connections from the thermopile at the gas valve terminals are

 

 

 

 

 

 

 

 

tight and that the thermopile is fully inserted into the pilot bracket.

 

 

 

 

Check the thermopile with a millvolt meter. Take the reading at TH-TP&TP

 

 

 

 

terminals of the gas valve. The meter should read 325 millivolts minimum, while

 

 

 

 

holding the valve knob depressed in the pilot position, with the pilot lit, and the

 

 

 

 

ON/OFF switch in the OFF position. Replace the faulty thermopile if the reading is

 

 

 

 

below the specified minimum.

 

 

 

 

With the pilot in the ON position, disconnect the thermopile leads from the valve.

 

 

 

 

Take a reading at the thermopile leads. The reading should be 325 millivolts

 

 

 

 

minimum. Replace the thermopile if the reading is below the minimum.

 

 

c. Defective valve.

 

Turn the valve knob to the ON position. Place the ON/OFF switch in the ON

 

 

 

 

position. Check the millivolt meter a the thermopile terminals. The millivolt meter

 

 

 

 

should read greater than 125mV. If the reading is acceptable, and if the burner

 

 

 

 

does not come on, replace the gas valve.

 

 

d. Plugged burner

 

Check the burner orifice for stoppage. Remove stoppage.

 

 

orifice.

 

 

 

 

e. Wall switch or

 

Follow the corrective action in Symptom and Possible Cause 1.a above. Check

 

 

wires are defective.

 

the switch and wiring. Replace where defective.

Quadra-FireQVI-30FB2020-900 Rev. H • 9/07

23

Page 23
Image 23
Quadra-Fire QVI-30FB owner manual Troubleshooting