Horizontal Through-the-Wall and Direct Venting (Category IV)
Fig. 25: Horizontal Through-the-Wall Venting
Fig. 26: Alt. Horizontal Through-the-Wall Venting
NOTE: While a drain connection is required in the vent of all XTherm installations, the drain can be ac- complished in several different ways. The figures in this manual show the drain in a vent tee, however, this can also be accomplished using an inline collec- tor for condensing stacks or an inline vertical or horizontal collector available from several of the listed vent manufacturers.
Fig. 27: Horizontal Through-the-Wall Direct Venting
CAUTION: This venting system requires the installation of a condensate drain in the vent piping per the vent manufacturer’s instructions. Failure to install a condensate drain in the venting system will void all warranties on this heater.
Installation
These installations utilize the
The total length of the horizontal
•75’ of straight flue pipe
•65’ of straight flue pipe and one elbow
•55’ of straight flue pipe and two elbows
•45’ of straight pipe and three elbows
The vent cap is not considered in the overall length of the venting system.