Recommended Settings for
Pool Heater (WHP) Applications
Item Modes Recommended
Setting
Boil Target 2 78°F
Boil Max 2 86°F
Boil Min 2 70°F
‘Burner’ Delay All 0:00 min
Boil Mass All 1 (Low)
Diff 2 2°F
‘Pump’ Dly All 3:00 min
Units All °F
Mode N/A 2
TableO: Recommended Temperature Control
Setpoints—WHP Models
34
Fig. 38: Mode 7 Primary/Secondary Piping with
External TargetTemp
*Maximum4 times the pipe diameter or 12”, whichever is less.
Mode 6 – Primary piping is prohibited.
Mode 7 – Designed for an external input signal with
primary/secondary piping. The external input signal
can be provided from a BMS, an EMS or a sequenc-
ing control. The external input signal changes the
boiler target according to a linear scale. The control
operates the boiler burner to maintain the boiler target
at the remote system sensor. See Fig. 38.
Mode 8 – This mode is for remote firing control of the
heater via an external sequencer such as the Raypak
TempTracker MOD+. The Boil Max setting is the
heater shutdown temperature (max temperature). The
heateris enable d via dry contact at the Enable/Disable
connectionat the low voltage terminal strip, and the fir-
ing rate is controlled by a 0-10 VDC signal from the
external sequencer. A control signal of ≥0.5 VDC
equates to minimum fire, and a signal of 10 VDC
equates to 100% firing rate.

*

RAYPAK
MODULATING
TEMPCONTROL
OUTDOOR AIR
SENSOR
*Maximum4 times the pipe diameter or 12”, whichever is less.
Fig. 39: Mode 8 Primary/Secondary Piping with
External Direct Drive
*
RAYPAK
MODULATING
TEMPCONTROL
NOTE: For Modes 7 and 8, connect to pins 13 and
14on the low-voltage pane l. Seepage 21. Use these
modes for systems using an external signal.