Rank Item Field Number Field Type FaultDescription
0 E01 Err Error EEPROM error
1 FPErr Warning Flame proof warning
2 BOIL OUT SHr Error Boiler outlet sensor short
3 BOIL OUT OPn Error Boiler outlet sensor open
4 BOIL IN SHr Error Boiler inlet sensor short
5 BOIL IN OPn Error Boiler inlet sensor open
6 SUP SHr Error System sensor short
7 SUP OPn Error System sensor open
8 OUTDR SHr Error Outdoor sensor short
9 OUTDR OPn Error Outdoor sensor open
10 DHW SHr Error DHW sensor short
11 DHW OPn Error DHW sensor open
TableS: Error Codes
UNITS - Selects the temperature units to be displayed
(°F or °C).
WWSD - Selects the outdoor temperature that shuts
the heater off,no matter what the demand. NOTE: The
WWSD segment is displayed on the LCD.

Operation

The Raypak modulating temperature control uses a
Liquid Crystal Display (LCD) as a method of supply-
ing information. The LCD is used to setup and monitor
system operation by means of three push buttons
(Item,Land M) shown at the bottom of Fig. 40.
All items displayed by the control are organized into
two menus, the view menu and the adjust menu. The
active menu is displayed in the upper right hand side
of the display in the menu field. The default menu is
the view menu.
When the temperature control is powered up, the con-
trol turns on all segments in the display for 2 seconds,
then the software version is displayed for 2 seconds.
At the end of that 4 second period, the control enters
the normal operating mode and “VIEW” is displayed.
Pressing the scroll button “scrolls” through the dis-
played values in the “VIEW” menu.
To make an adjustment to a setting in the control,
begin by selecting the “ADJUST” menu. To change
from the view menu to the adjust menu, simultaneous-
ly press and hold all three buttons for 1 second. The
menu name, “ADJUST” will be displayed in the menu
field.
The menu will automatically revert back to the view
menu after 20 seconds of keyboard inactivity. Then
scroll to the desired item using the scroll button. Fi-
nally,use the Lor Mbutton to make the adjustment.
In the absence of other information, the values pro-
vided in Tables R and S should be used as default
settings.
Modulating
Control

Item

DHW
Modulation
External Input
Signal
Offset
Fig. 40: Modulating TemperatureControl Display
ItemField
Displaysan
abbreviated
nameof the
selecteditem
Buttons
Selects
Menus,
Itemsand
adjusts
settings
MenuField
Displaysthe current menu
{
NumberField
Displaysthe
currentvalue of
theselected
item
StatusField
Displaysthe
currentstatus
ofthe control’s
inputs,outputs
andoperation