CAUTION: When condensate traps are installed, condensate must be routed to an appropriate container for neutralization before disposal, as required by local codes.

WARNING: Contact the manufacturer of the vent material if there is any question about the appliance categorization and suitability of a vent material for application on a Category III or IV vent system. Using improper venting materials can result in personal injury, death or property damage.

Support of Vent Stack

The weight of the vent stack or chimney must not rest on the heater vent connection. Support must be pro- vided in compliance with applicable codes. The vent should also be installed to maintain proper clearances from combustible materials.

Use insulated vent pipe spacers where the vent pass- es through combustible roofs and walls.

Vent Terminal Location

NOTE: During winter months check the vent cap and make sure no blockage occurs from build-up of snow or ice.

1.Condensate can freeze on the vent cap. Frozen condensate on the vent cap can result in a blocked flue condition.

2.Give special attention to the location of the vent termination to avoid possibility of property dam- age or personal injury.

3.Gases may form a white vapor plume in winter. The plume could obstruct a window view if the ter- mination is installed near windows.

4.Prevailing winds, in combination with below-freez- ing temperatures, can cause freezing of condensate and water/ice build-up on buildings, plants or roofs.

5.The bottom of the vent terminal and the air intake shall be located at least 12 in. above grade, includ- ing normal snow line.

6.Un-insulated single-wall metal vent pipe shall not be used outdoors in cold climates for venting gas- fired equipment.

7.Through-the-wall vents for Category II and IV appliances and non-categorized condensing appli- ances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimen- tal to the operation of regulators, relief valves, or other equipment. Where local experience indi- cates that condensate is a problem with Category I and III appliances, this provision shall also apply.

Combustion

Air Supply

Exhaust

Configuration

Heater Venting

Category

Certified Materials

Combustion Air

Inlet Material

 

Vertical Natural

I

“B” Vent

 

 

From Inside Building

Draft Venting

 

 

 

 

 

 

(Non-Direct Venting)

Horizontal Through-

III

Stainless Steel

 

 

 

 

 

 

the-Wall Venting

(Gas Tight)

 

 

 

 

 

 

 

Vertical Natural

I

“B” Vent

Galvanized Steel

From Outside Building

Draft Venting

 

PVC

 

 

 

(Direct Venting)

Horizontal Through-

III

Stainless Steel

 

ABS

 

 

CPVC

 

the-Wall Venting

(Gas Tight)

 

 

 

 

 

 

 

 

 

 

 

Table M: Venting Category Requirements

26

Page 26
Image 26
Raypak 902B, 302B manual Support of Vent Stack, Vent Terminal Location

302B, 902B specifications

Raypak is a prominent name in the heating industry, particularly known for its advanced technology and robust design in residential and commercial heating solutions. Two of their notable models, the Raypak 302B and 402B, exemplify innovation and efficiency in hydronic heating systems, designed to meet diverse needs while ensuring optimal performance.

The Raypak 302B and 402B are high-efficiency boilers that utilize gas-fueled systems. The 302B model has a heating capacity of 302,000 BTU/h, while the 402B boasts a maximum capacity of 402,000 BTU/h. This range of heating output makes these models suitable for a variety of applications, from residential heating needs to larger commercial spaces that require a reliable heat source.

One of the standout features of the Raypak 302B and 402B is their use of fire-tube heat exchanger technology. This design promotes efficient heat transfer and allows for lower emissions, thus minimizing the environmental impact. The fire-tube design also contributes to a longer lifespan and reduced maintenance costs, making these boilers a cost-effective solution over time.

Equipped with advanced control systems, the Raypak 302B and 402B ensure precise temperature regulation and improved energy usage. The digital display provides real-time feedback and diagnostics, enhancing user experience and simplifying troubleshooting. These models are also compatible with various building management systems, providing users with versatility in integration to optimize building performance.

In addition to their technological advancements, these boilers are designed with user safety and convenience in mind. They include features such as built-in safety controls, easy access for service and maintenance, and a compact footprint to fit into tight spaces. Their robust construction ensures durability, which is crucial for systems that operate under high demand.

Moreover, both models have been engineered to succeed in various climates, making them reliable choices for users in diverse geographical locations. With their energy-efficient operation, reliable performance, and advanced features, the Raypak 302B and 402B embody quality and innovation in the heating market, ensuring comfortable environments while lowering energy costs and environmental footprints.