Raypak 302B, 902B manual Table R UDB Fault Messages, Hi Delta, Delay, LCD Display Without Fault

Models: 302B 902B

1 60
Download 60 pages 4.29 Kb
Page 39
Image 39
Hi Delta

 

 

 

Detection

 

 

 

Hi Delta

Delay

 

LCD Display Readout With Fault

 

 

 

 

 

Cond Drain Blocked/Vent Temp Limit Err

PVC Vent Limit-CHX

1

 

Check Drain Switch, Check Drain/Check Vent System

 

 

 

 

 

Man Hi Limit Fault

Manual High Limit

1

 

Confirm Settings, Reset Hi Limit

 

 

 

 

 

Auto Hi Limit Fault

Auto High Limit

1

 

Confirm Settings, Check Pump

 

 

 

 

 

Lo Water Cutoff Err

 

 

 

 

 

Purge Air, Check Pump, Chk Isolation Valve,

Low Water Cut-off

1

 

Reset LWCO

 

 

 

 

 

Vent Pressure Fault

Vent Pressure

1

 

Blocked Vent, Check Vent System

 

 

 

 

 

Lo Gas Press Fault

Low Gas Pressure

1

 

Confirm Settings, Check Supply Gas, Reset LGPS

 

 

 

 

 

Hi Gas Press Fault

High Gas Pressure

1

 

Confirm Settings, Check Supply Gas,

 

 

 

 

 

Controller Alarm

Controller Alarm

1

 

See Control Display

 

 

 

 

 

Water Flow Sw Fault

 

Flow Switch

3

 

Check Boiler Pump, Purge Air, Replace Flow Switch

 

 

 

 

 

Blower Air Sw. Fault

Blower Switch

3

 

Check Air Filter, Check Blower, Check Air Sw. Hose

 

 

 

 

 

Factory Option Fault

 

 

 

 

 

Check Factory Data, Check Wiring Diagram, Check

 

 

 

 

 

Freeze Control, Check Water Pressure

Factory Option

3

 

 

 

 

 

 

 

Field Interlock Err

 

 

 

 

 

Check Louvers, Check Comb. Damper, Check

External Interlock

90

 

Extractor Sw.

 

 

 

 

 

 

 

CWS/CWR Fault

 

CWS/CWR

3

 

Confirm Inlet Temp, Reset CWS/CWR Cntrl

 

 

 

 

 

Ignition Lockout

 

 

 

 

 

Display actual Fault Flash Code

 

 

 

 

 

Recycle/Reset Control, Push Reset Button

Ignition Lockout

1

 

See Table Below

 

 

 

 

 

 

Field

 

 

 

 

 

Interlock #

Fault

 

 

 

Flashes

 

 

 

LCD Display Readout With Fault

1

 

Low Air

 

 

Low Air Fault

 

 

 

 

Check Blower, Check Filter, Check Air Sw. Hose

2

 

Flame - No CFH

 

 

Flame - No CFH

 

 

 

 

 

Shut Off Gas Supply, Recycle Power

3

 

Ignition Lockout

 

 

Ignition Lockout

 

 

 

 

 

Recycle/Reset Cntrl, Push Reset Button

4

 

Low HSI Current

 

 

Low HSI Current

 

 

 

Check HSI Current, Replace HSI, Recycle Power, Replace Ign.

5

 

Low 24VAC

 

 

Low 24 VAC

 

 

 

 

 

Check Power Supply, Check Transformer

6

 

Internal Cntrl Fault

 

 

Internal Cntrl Fault

 

 

 

 

 

Recycle/Reset Cntrl, Replace Control

 

 

 

 

 

 

 

Condition

 

 

LCD Display Without Fault

Power On / No CFH

 

 

System Normal

 

 

Standby / WebSite*

Power On / CFH

 

 

System Normal

 

 

CFH Active / WebSite*

 

 

 

*Toggles Between /

Table R: UDB Fault Messages

39