![High Limit (Manual Reset)](/images/new-backgrounds/35581/3558173x1.webp)
High Limit (Manual Reset)
The heater is equipped with a manual reset high limit temperature device. Push the reset button and adjust the setting to 40 - 50°F above desired operating tem- perature.
Low Water Cut-Off (Optional)
The low water
Fig. 30: High Limit (Manual Reset)
Flow Switch
This
Fig. 32: Low Water
High and Low Gas Pressure Switches
The low gas pressure switch (optional) connection mounts upstream of the gas valve to ensure that suffi- cient gas pressure is present for proper regulator performance. The low gas pressure switch automati- cally shuts down the heater if gas supply drops below the recommended setting of 5.0 in. WC for natural gas, and 10.0 in. WC for propane gas.
The high gas pressure switch (optional) connection mounts downstream of the
Fig. 31: Flow Switch
Operating Control
The heater may be equipped with different types of |
| |
operating controls. Consult the individual control data |
| |
sheets supplied with your heater paperwork. See the |
| |
General Safety Section for safety precautions con- | Fig. 33: High/Low Gas Pressure Switch | |
cerning domestic hot water applications. | ||
|
37