START-UP

START-UP

Pre Start-up

Filling System (Heating Boilers)

Fill system with water. Purge all air from the system. Lower system pressure. Open valves for normal sys- tem operation, and fill system through feed pressure. Manually open air vent on the compression tank until water appears, then close vent.

Air Purge (Domestic Hot Water Heaters)

Purge all air from system before lighting heater. This can be normally accomplished by opening a down- stream valve.

NOTE: Boil-out information: The oils, grease and other contaminates found in some gas fired boilers are not present in the water side of a Raypak appliance. Most boil-out procedures require the use of an alkaline (high pH) cleaning agent that will damage the copper finned tubes of the heat exchanger. Heat exchangers damaged due to boil- out are not covered under warranty.

Venting System Inspection

1.Check all vent pipe connections and flue pipe ma- terial.

2.Make sure vent terminations are installed per code and are clear of all debris or blockage.

For Your Safety

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

This appliance has a hot surface igniter. It is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand.

BEFORE OPERATING, smell all around the appliance area for gas. Be sure to smell near the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS:

Do not try to light any appliance.

Do not touch any electrical switch; do not use any telephone in your building.

Immediately call your gas supplier from a neigh- bor’s telephone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

Use only your hand to push in or turn the gas con- trol knob. Never use tools. If the knob will not turn by hand, do not try to repair it, call a qualified serv- ice technician. Forced or attempted repair may result in a fire or explosion.

Do not use this appliance if any part has been under water, immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

Check around unit for debris and remove com- bustible products, i.e. gasoline, etc.

Pre Start-up Check

1.Verify heater is filled with water.

2.Check system piping for leaks. If found, repair immediately.

3.Vent air from system. Air in system can interfere with water circulation.

4.Purge air from gas line up to heater.

Initial Start-up

Tools Needed

(1) 12-0-12, 24” scale U-tube manometer

(4) 6-0-6, 12” scale U-tube manometers (mini- mum)

(1) Screwdriver

(1) Multi-meter

(1) 3/16” Allen wrench

NOTE: Digital manometers are not recommended.