Raypak HD401 Gas Supply Pressure, Gas Pressure Regulator, Table G Maximum Equivalent Pipe Length

Models: HD101 HD401

1 48
Download 48 pages 22.97 Kb
Page 18
Image 18
Gas Supply Pressure

Fig. 13: Sediment Trap Orientation

CAUTION: Do not use Teflon tape on gas line pipe thread. A pipe compound rated for use with gas systems is recommended. Apply sparingly only on male pipe ends.

CAUTION: Support gas supply piping with hangers, not by the heater or its accessories. Ensure the gas piping is protected from physical damage and freezing where required.

Gas Supply Pressure

A minimum of 4 in. WC and a maximum of 10.5 in. WC upstream gas pressure is required under load and no load conditions for natural gas. A minimum of 11 in. WC and a maximum of 13 in. WC is required for propane gas. The gas pressure regulator supplied on the heater is for low pressure service. If upstream

pressure exceeds 14 in. WC, an intermediate gas pressure regulator, of the lockup type, must be installed.

When connecting additional gas utilization equipment to the gas piping system, the existing piping must be checked to determine if it has adequate capacity.

Gas Pressure Regulator

The gas valve pressure regulator(s) on the heater are nominally preset at 3 in. WC for natural gas, and 10.0 in. WC for propane gas manifold pressure. The pres- sure at the gas valve outlet tap, measured with a manometer, while in operation should be 3.0 in. ± 0.3 in. WC (HI), and 1.0 in. ± 0.1 WC (LO) for natural gas and 10.0 in. ± 0.1 in. WC (HI), and 3.5 in. ± 0.1 in. WC (LO) for propane gas. If an adjustment is needed, turn the adjustment screw clockwise to increase pressure or counter-clockwise to decrease pressure.

Model

Input

3/4”

 

1”

1-1/4”

1-1/2”

 

 

 

 

 

 

 

 

 

 

No.

(KBTUH)

N

P

N

 

P

N

P

N

P

 

 

 

 

 

 

 

 

 

 

 

 

 

HD101

100

105

385

340

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HD151

150

50

180

160

 

530

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HD201

199

30

95

95

 

355

360

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HD251

250

20

50

60

 

230

240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HD301

299

15

35

45

 

170

170

550

360

 

 

 

 

 

 

 

 

 

 

 

 

HD401

399

5

20

25

 

80

100

365

210

 

 

 

 

 

 

 

 

 

 

 

 

Natural gas – 1,000 BTUH per ft3, .60 specific gravity at 0.5 in. WC pressure drop Propane gas – 2,500 BTUH per ft3, 1.50 specific gravity at 0.5 in. WC pressure drop

Table G: Maximum Equivalent Pipe Length

18

Page 18
Image 18
Raypak HD401, HD101 manual Gas Supply Pressure, Gas Pressure Regulator, Table G Maximum Equivalent Pipe Length