Raypak HD401 Electrical Connections - Domestic Hot Water, Single Stage Tankstat Stage Connection

Models: HD101 HD401

1 48
Download 48 pages 22.97 Kb
Page 20
Image 20
Electrical Connections — Domestic Hot Water

Electrical Connections — Domestic Hot Water

DANGER—SHOCK HAZARD: Make sure electrical power to the heater is disconnected to avoid potential serious injury or damage to components.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

NOTE: Minimum 18 AWG, 105°C, stranded wire must be used for all low voltage (less than 30 volts) external connections to the unit. Solid conductors should not be used because they can cause excessive tension on contact points. Install conduit as appropriate. All high voltage wires must be the same size (105°C, stranded wire) as the ones on the unit or larger.

Installer action is required to electrically enable your Hi Delta heater to operate after making the power con- nections. You must make a connection on Terminal Block #3 for temperature control connections. This will be done based on the controller option selected with your heater order.

For operation with a Temp-Tracker controller, refer to the Temp-Tracker Installation and Operating Instructions, Raypak Catalog number 5000.66 (P/N 241177).

Consult the wiring diagram shipped with the heater in the instruction packet. The Stage 1 connections are for the remote tank control through the heaters 24 volt transformer. DO NOT attach line voltage to the Stage 1 connection. Before starting heater, check to ensure proper voltage to heater and pump.

SINGLE

STAGE

TANKSTAT

STAGE 1

CONNECTION

ATTACH STAGE 1 CONNECTIONS

ON HEATER TO THE SINGLE STAGE

TANKSTAT AS SHOWN IN THE DIAGRAM ABOVE.

Fig. 15: Single Stage Tankstat

2-STAGE

TANKSTAT

STAGE 1

 

 

 

 

STAGE 2 CONNECTION OR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STAGE 1 CONNECTION

CONNECTION

 

 

 

 

 

 

 

 

OF HEATER 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATTACH STAGE 1 CONNECTIONS ON HEATER TO STAGE 1 CONNECTION ON TANKSTAT.

ATTACH STAGE 2 CONNECTIONS OR STAGE 1 CONNECTION OF HEATER 2 TO STAGE 2 CONNECTIONON TANKSTAT AS SHOWN IN THE DIAGRAM.

Fig. 16: 2-Stage Tankstat

20

Page 20
Image 20
Raypak HD401, HD101 manual Electrical Connections - Domestic Hot Water, Single Stage Tankstat Stage Connection