Electrical Power Connections
Installations must follow these codes:
·National Electrical Code and any other national, state, provincial or local codes or regulations hav- ing jurisdiction
·Safety wiring must be N.E.C. Class 1
·Heater must be electrically grounded as required by N.E.C.
·In Canada, C22.1
The heater is wired for 120 VAC, less than 12 AMPS. The voltage is indicated on the
Install a separate disconnect means for each load. Use
It is strongly recommended that all
Surge Protection
If any of the original wire as supplied with the heater must be replaced, it must be replaced with 105°C wire or its equivalent.
Check the Power Source
WARNING: Using a
AC = 108 Volts AC Minimum, 132 Volts AC MAX AB = 108 Volts AC Minimum, 132 Volts AC MAX BC = < 1 Volt AC
Fig. 14: Check Power Source
Making the Electrical Connections
Refer to Fig. 14 and the Wiring Diagram.
1.Verify circuit breaker is properly sized by referring to heater rating plate. A dedicated circuit breaker should be provided.
2.Turn off all power to the heater. Verify that power has been turned off by testing with a
3.Observe proper wire colors while making electrical connections. Many electronic controls are polarity sensitive. Components damaged by improper electrical installation are not covered by warranty.
4.Provide an external surge suppressor capable of maintaining system integrity.
5.Provide overload protection and a disconnect means for equipment serviceability as required by local and state code.
6.Install heater controls, thermostats, or building management systems in accordance with the applicable manufacturer’s instructions.
7.Conduit should not be used as the ground. There must be a solidly wired ground.
NOTE: A grounding electrode conductor shall be used to connect the equipment grounding conductors, the equipment enclosures, and the grounded service conductor to the grounding electrode.
19